Daikin Mini-Split Code H6

Soft lockout

Position sensor abnormality - the compressor failed to start. The position-detection circuit could not establish the compressor's rotor position at start-up.

Manual wording: “H6 Position sensor abnormality

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units

Likely causes, most common first

  1. Start-up failure caused by the closed stop valve
  2. Input voltage is outside the specified range
  3. Disconnection of the compressor relay cable
  4. Defective compressor
  5. Defective outdoor unit PCB

What you can safely check yourself

  • Check the breaker or disconnect for the outdoor unit is fully on
  • Turn the system off at the breaker or disconnect switch, leave it off at least 30 seconds, and turn it back on once

When to call a technician

H6 needs supply voltage and discharge pressure measured at the outdoor unit. A closed stop valve left over from installation is a common cause and only a technician should open it.

A Daikin mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.