HVAC Code Lookup

Daikin fault codes

58 documented codes for Daikin mini-splits, each cited to the manufacturer's own manual. Find your code in the table, then jump to what it means, the likely causes, what you can safely check, and when to call a technician.

Daikin uses one alphanumeric error-code set across its residential ductless line. The same table appears in the FTXS-L / FDXS-L pair service manual, the H-Series (FTXS/RKS-HVJU) pair manual, the FTXM-W/V (Atmosphera) manual, and the RMXS multi-split manual, so an A5 or U4 on a 2015 FTXS wall-mount means the same thing as on a current Atmosphera. Multi-zone systems (MXS / RMXS with Branch Provider units) add transmission and address codes (U9, UF, UH, UC, UE) that pair systems never show, and a few codes are re-used with a different meaning on multi-zone hardware (E5 and F6 in particular). Codes are read on the wireless remote's temperature display using the unit's service-check / code-retrieval mode, not on the indoor unit itself.

Mini-Split codes

CodeMeaningSeverity
00NormalStatus
A1Indoor unit PCB abnormalityHard lockout
A3Drain level control system abnormalitySoft lockout
A5Freeze-up protection control or heating peak-cut controlWarning
A6Indoor fan motor or related abnormalitySoft lockout
C4Indoor heat exchanger thermistor or related abnormalityWarning
C5Indoor heat exchanger thermistor 2 or related abnormalityWarning
C7Front panel open/close faultWarning
C9Room temperature thermistor or related abnormalityWarning
CCHumidity sensor abnormalityWarning
CEPresence sensor or floor sensor abnormalityWarning
CJRemote controller thermistor abnormalityWarning
E1Outdoor unit PCB abnormalityHard lockout
E3Actuation of high pressure switchSoft lockout
E4Actuation of low pressure sensorSoft lockout
E5On pairSoft lockout
E6Compressor lockHard lockout
E7DC fan lockSoft lockout
E8Input overcurrent detectionSoft lockout
E9Moving part of electronic expansion valveSoft lockout
EAFour way valve abnormalitySoft lockout
F3Discharge pipe temperature controlSoft lockout
F6On pair systems, high pressure control in cooling - the outdoor coil sensor went above about 140-149F so the unit cut back or haltedWarning
F8System shutdown due to compressor internal temperature abnormalityHard lockout
H0Compressor system sensor abnormalitySoft lockout
H6Position sensor abnormality - the compressor failed to startSoft lockout
H8DC voltage or current sensor abnormality on 09/12 class units, or CTSoft lockout
H9Outdoor temperature thermistor or related abnormalityWarning
J3Discharge pipe thermistor or related abnormalityWarning
J5Suction pipe thermistorWarning
J6Outdoor heat exchanger thermistor or related abnormalityWarning
J7Outdoor liquid pipe thermistorWarning
J8Liquid pipe thermistor or related abnormalityWarning
J9Subcooling heat exchanger gas pipe thermistorWarning
JAHigh pressure sensor abnormalityWarning
JCLow pressure sensor abnormalityWarning
L1Outdoor unit PCB abnormality on the inverter sideHard lockout
L3Electrical box temperature riseSoft lockout
L4Radiation fin temperature riseSoft lockout
L5Output overcurrent detectionHard lockout
L8Inverter current abnormalitySoft lockout
L9Compressor start-up errorSoft lockout
P1High voltage of capacitor in main inverter circuitSoft lockout
P4Radiation fin thermistor or related abnormalityWarning
U0Refrigerant shortageWarning
U2Low-voltage detection or over-voltage detectionWarning
U3Check operation is not conductedWarning
U4Signal transmission error between the indoor unit and the outdoor unitSoft lockout
U5Signal transmission error between the indoor unit and the remote controllerWarning
U7Signal transmission error on the outdoor unit PCBSoft lockout
U8Signal transmission error between the MAIN remote controller and the SUB remote controllerWarning
U9Signal transmission error between an indoor unit and the outdoor unit within the same multi-zone systemSoft lockout
UAOn pair systems, unspecified voltage between indoor and outdoor unit - a pair-type and a multi-type unit have been connected togetherSoft lockout
UCAddress duplication of central remote controllerWarning
UETransmission error between the centralized remote controller and an indoor unitWarning
UFSystem is not set yetSoft lockout
UHSystem abnormality, refrigerant system address undefinedSoft lockout
Operation lamp blinkingGreen OPERATION lamp on the indoor unit blinking continuouslyThe green OPERATION lamp on the face of the indoor unit blinks when the unit has detected a faultWarning

Daikin mini-split code 00: Normal

Status

Normal. 00 is what the remote shows in service-check mode when the system has no stored error. If you go through the code-retrieval procedure and land on 00 with a long beep, the control is not reporting a fault.

Manual wording: “System 00 Normal”

Documented for: All Daikin residential ductless with wireless remote service-check mode

Likely causes, most common first

  1. No fault stored in the control
  2. The problem is intermittent and cleared itself
  3. The complaint is a comfort or airflow issue rather than a control fault

What you can safely check yourself

  • Check the remote is in the mode and temperature you expect
  • Check and replace the indoor unit air filter
  • Make sure supply and return airflow at the indoor unit is not blocked by furniture or curtains
  • Check the outdoor unit is clear of leaves, snow and debris

When to call a technician

If comfort is poor but no code is stored, a technician needs to check refrigerant charge and airflow with gauges - there is nothing further a homeowner can read off the remote.

Sources

Daikin mini-split code A1: Indoor unit PCB abnormality

Hard lockout

Indoor unit PCB abnormality. The indoor unit's microcomputer checked itself and either the internal circuit is not working or it cannot load its internal settings.

Manual wording: “Indoor A1 Indoor unit PCB abnormality”

Documented for: FTXS-L, FDXS-L, H-Series, FTXM-W/V (Atmosphera), RMXS multi-split indoor units

Likely causes, most common first

  1. Wrong models interconnected (indoor and outdoor unit are not a matched pair)
  2. Defective indoor unit PCB
  3. Disconnection of a connector on the indoor PCB
  4. Reduction of power supply voltage

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once
  • Check the breaker for the indoor and outdoor unit is fully on

When to call a technician

A1 is an indoor control board fault. Checking connectors, supply voltage and model compatibility means opening the indoor unit electrical box, which is a technician's job.

Sources

Daikin mini-split code A3: Drain level control system abnormality

Soft lockout

Drain level control system abnormality. The condensate float switch detected water at its upper limit and turned off, so the unit stops to avoid overflowing.

Manual wording: “A3 Drain level control system abnormality”

Documented for: Ducted, cassette and other indoor units with a condensate pump (FDXS/CDXS/FFQ on RMXS multi-split systems)

Likely causes, most common first

  1. Defective drain pump
  2. Improper drain piping work
  3. Clogged drain piping
  4. Defective float switch
  5. Defective indoor unit PCB
  6. Defective short circuit connector X15A on indoor unit PCB

What you can safely check yourself

  • Check the condensate drain line outlet outside for a clog, kink or blockage
  • Check for water pooling under the indoor unit and shut the system off if it is overflowing
  • Turn the system off at the breaker or disconnect switch and back on once after the drain is clear

When to call a technician

If the drain line is clear and A3 comes back, the drain pump or float switch is failing and needs a technician - a plugged drain that keeps refilling will damage the unit and the wall.

Source

Daikin mini-split code A5: Freeze-up protection control or heating peak-cut control

Warning

Freeze-up protection control or heating peak-cut control. In cooling, the indoor coil dropped below 32F and the unit halted so the coil does not ice over. In heating, the indoor coil went above roughly 140-149F and the unit cut back or halted.

Manual wording: “A5 Freeze-up protection control or heating peak-cut control”

Documented for: FTXS-L, FDXS-L, H-Series, FTXM-W/V (Atmosphera), RMXS multi-split indoor units

Likely causes, most common first

  1. Clogged air filter of the indoor unit
  2. Short-circuited air (discharge air blowing straight back into the return)
  3. Dust accumulation on the indoor heat exchanger
  4. Defective indoor heat exchanger thermistor
  5. Defective indoor unit PCB

What you can safely check yourself

  • Check and clean or replace the indoor unit air filters - this is the number one cause
  • Make sure nothing is blocking the indoor unit's air intake or discharge (furniture, curtains, shelving)
  • Give the unit time to thaw with the fan running before restarting
  • Check the outdoor unit is not buried in snow or leaves

When to call a technician

If A5 returns with clean filters and clear airflow, the indoor coil is dirty or the system is low on refrigerant - both need a technician. Do not keep restarting a unit that is icing up.

Sources

Daikin mini-split code A6: Indoor fan motor or related abnormality

Soft lockout

Indoor fan motor or related abnormality. The Hall IC in the indoor blower reports a speed that never reaches the commanded speed and stays below half of the motor's maximum, so the control declares a fan fault.

Manual wording: “A6 Fan motor or related abnormality”

Documented for: FTXS series (DC motor), FDXS series (AC motor), H-Series, FTXM-W/V, RMXS indoor units

Likely causes, most common first

  1. Layer short inside the fan motor winding
  2. Breaking of wire inside the fan motor
  3. Breaking of the fan motor lead wires
  4. Defective capacitor of the fan motor (AC motor / FDXS ducted units)
  5. Reduction of power supply voltage (AC motor units)
  6. Defective indoor unit PCB

What you can safely check yourself

  • Check nothing has fallen into or is jamming the indoor unit's air outlet
  • Check and clean or replace the air filters
  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

A6 means the blower is not turning at the speed the board asked for. Testing the motor, its capacitor and the board requires opening the indoor unit's electrical box - call a technician.

Sources

Daikin mini-split code C4: Indoor heat exchanger thermistor or related abnormality

Warning

Indoor heat exchanger thermistor or related abnormality. The sensor reading the indoor coil temperature is sending a voltage above 4.96 V or below 0.04 V, which means it is open or shorted.

Manual wording: “C4 Indoor heat exchanger thermistor or related abnormality”

Documented for: FTXS-L, FDXS-L, H-Series, FTXM-W/V, RMXS indoor units

Likely causes, most common first

  1. Disconnection of connector
  2. Defective thermistor
  3. Defective indoor unit PCB

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

C4 is a failed or disconnected temperature sensor inside the indoor unit. A technician has to measure the thermistor's resistance and reseat or replace it.

Sources

Daikin mini-split code C5: Indoor heat exchanger thermistor 2 or related abnormality

Warning

Indoor heat exchanger thermistor 2 or related abnormality. The second indoor coil sensor is reading open or shorted (voltage at or above 4.96 V, or at or below 0.04 V, during compressor operation).

Manual wording: “C5 Indoor heat exchanger thermistor 2 or related abnormality”

Documented for: Indoor units with a second coil thermistor on RMXS multi-split systems

Likely causes, most common first

  1. Disconnection of connector
  2. Thermistor corresponding to the error code is defective
  3. Defective indoor unit PCB

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

Same as C4 - a technician needs to check the sensor connector and resistance inside the indoor unit.

Source

Daikin mini-split code C7: Front panel open/close fault

Warning

Front panel open/close fault. On models with a motorized front panel, the panel did not move to the position the control commanded.

Manual wording: “C7 Front panel open/close fault”

Documented for: CTXG09/12/18QVJUW(S) designer wall-mount units

Likely causes, most common first

  1. Defective reduction motor
  2. Malfunction or deterioration of the front panel mechanism
  3. Defective limit switch

What you can safely check yourself

  • Check nothing is physically blocking the front panel from opening or closing
  • Turn the system off at the breaker or disconnect switch and back on once, then watch whether the panel moves

When to call a technician

If the panel still will not move, the panel motor or limit switch needs replacing. Do not force the panel by hand.

Source

Daikin mini-split code C9: Room temperature thermistor or related abnormality

Warning

Room temperature thermistor or related abnormality. The sensor that reads room air temperature at the indoor unit is open or shorted.

Manual wording: “C9 Room temperature thermistor or related abnormality”

Documented for: FTXS-L, FDXS-L, H-Series, FTXM-W/V, RMXS indoor units

Likely causes, most common first

  1. Disconnection of connector
  2. Defective thermistor
  3. Defective indoor unit PCB

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

C9 is a failed room sensor in the indoor unit. A technician has to check the connector and the thermistor's resistance value.

Sources

Daikin mini-split code CC: Humidity sensor abnormality

Warning

Humidity sensor abnormality. The indoor unit's humidity sensor is not communicating or has failed.

Manual wording: “CC Humidity sensor abnormality”

Documented for: FTXM-W/V (Daikin Atmosphera)

Likely causes, most common first

  1. Disconnection of connector
  2. Defective humidity sensor
  3. Defective indoor unit PCB

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

The humidity sensor PCB is inside the indoor unit and has to be reseated or replaced by a technician.

Source

Daikin mini-split code CE: Presence sensor or floor sensor abnormality

Warning

Presence sensor or floor sensor abnormality. The optional occupancy/floor-temperature sensor kit read as disconnected or shorted while the unit was running.

Manual wording: “CE Presence sensor or floor sensor abnormality”

Documented for: Indoor units fitted with the intelligent eye / floor sensor kit

Likely causes, most common first

  1. Disconnection of connector
  2. Breaking of wires
  3. Defective sensor(s)
  4. Defective sensor kit PCB

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

The sensor kit plugs into connector X81 on the indoor PCB - reseating or replacing it is a technician's job. The unit will usually still heat and cool without the sensor.

Source

Daikin mini-split code CJ: Remote controller thermistor abnormality

Warning

Remote controller thermistor abnormality. The temperature sensor built into the wired wall controller read open or shorted. The system can keep running using the indoor unit's own sensor.

Manual wording: “CJ Remote controller thermistor abnormality”

Documented for: Systems using a wired wall remote controller

Likely causes, most common first

  1. Defective room temperature thermistor in the wired remote controller
  2. Defective wired remote controller PCB
  3. External factor such as noise

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once and see whether CJ comes back

When to call a technician

If CJ keeps returning the wired controller needs replacing. Note the room temperature it senses will be off until then.

Source

Daikin mini-split code E1: Outdoor unit PCB abnormality

Hard lockout

Outdoor unit PCB abnormality. The outdoor control board's microprocessor ran out of control, or it is not seeing the zero-cross signal from the incoming power.

Manual wording: “Outdoor E1 Outdoor unit PCB abnormality”

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units, RMXS multi-split outdoor

Likely causes, most common first

  1. Defective outdoor unit PCB
  2. Broken harness between PCBs
  3. Noise
  4. Momentary fall of voltage
  5. Momentary power failure

What you can safely check yourself

  • Check for a recent power outage or brownout
  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once

When to call a technician

If E1 returns after a power cycle the outdoor control board is failing and needs replacing by a technician.

Sources

Daikin mini-split code E3: Actuation of high pressure switch

Soft lockout

Actuation of high pressure switch. The high-pressure safety switch opened because refrigerant discharge pressure climbed past its setpoint (about 4.15 MPa on Atmosphera, 4.0 MPa on RMXS).

Manual wording: “E3 Actuation of high pressure switch”

Documented for: FTXM-W/V (Atmosphera), RMXS multi-split outdoor units

Likely causes, most common first

  1. Actuation of the high pressure switch (S1PH)
  2. Closed stop valve
  3. Disconnection of connector S40 or of the two terminals at the high pressure switch
  4. Broken S1PH harness
  5. Defective high pressure switch
  6. Defective outdoor unit PCB
  7. Defective high pressure sensor (multi-split)
  8. Instantaneous power failure (multi-split)

What you can safely check yourself

  • Check the outdoor unit is not blocked by leaves, snow, plants or a fence and has open space around it
  • Check the outdoor coil is not visibly plugged with dirt or cottonwood
  • Turn the system off at the breaker or disconnect switch and back on once after clearing anything blocking airflow

When to call a technician

Stop valve position, pressure switch testing and refrigerant charge are all technician work. Never bypass or jumper the high-pressure switch.

Sources

Daikin mini-split code E4: Actuation of low pressure sensor

Soft lockout

Actuation of low pressure sensor. Suction pressure fell below about 0.07 MPa, so the control stopped the compressor.

Manual wording: “E4 Actuation of low pressure sensor”

Documented for: RMXS multi-split outdoor units

Likely causes, most common first

  1. Abnormal drop of low pressure (lower than 0.07 MPa)
  2. Defective low pressure sensor
  3. Defective outdoor unit PCB
  4. Stop valve not opened

What you can safely check yourself

  • Check and replace the indoor unit air filters (starved airflow drops suction pressure)
  • Make sure indoor unit airflow is not blocked
  • Check the outdoor unit is clear of snow and debris

When to call a technician

E4 usually means low refrigerant charge, a closed stop valve or a restriction. All of those need a technician with gauges.

Source

Daikin mini-split code E5: On pair

Soft lockout

On pair (single-zone) systems, OL activation - the compressor's overload protector tripped. On RMXS multi-split systems the same code means compressor motor lock: the compressor will not start even in forced start-up mode.

Manual wording: “E5 OL activation (compressor overload)”

Documented for: FTXS-L, H-Series, FTXM-W/V pair systems (compressor overload); RMXS multi-split (compressor motor lock)

Likely causes, most common first

  1. Refrigerant shortage
  2. Defective stop valve or stop valve left closed
  3. Defective discharge pipe thermistor
  4. Defective electronic expansion valve or coil
  5. Defective four way valve or coil
  6. Water mixed in refrigerant
  7. Defective outdoor unit PCB
  8. Compressor lock or high differential pressure (multi-split)
  9. Incorrect UVW wiring (multi-split)

What you can safely check yourself

  • Check the outdoor unit has clear airflow and is not blocked by snow, leaves or stored items
  • Check and replace the indoor unit air filters
  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

E5 points at the compressor and the refrigerant circuit. It needs a technician with gauges - repeated restarts on an overloaded compressor will kill it.

Sources

Daikin mini-split code E6: Compressor lock

Hard lockout

Compressor lock. The position-detection circuit shows the compressor is not turning when it should be - on 09/12 class units the compressor stops on overcurrent instead.

Manual wording: “E6 Compressor lock”

Documented for: FTXS-L, FDXS-L, H-Series, FTXM-W/V outdoor units

Likely causes, most common first

  1. Compressor locked
  2. Compressor harness disconnected

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch, leave it off at least 30 seconds, and turn it back on once

When to call a technician

E6 means the compressor is mechanically or electrically locked. Diagnosis takes an inverter checker on the U/V/W harness and usually ends in a compressor or board replacement.

Sources

Daikin mini-split code E7: DC fan lock

Soft lockout

DC fan lock (outdoor fan motor abnormality). The outdoor fan did not start within 15 to 30 seconds of being commanded to run.

Manual wording: “E7 DC fan lock”

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units, RMXS multi-split outdoor

Likely causes, most common first

  1. Foreign matter stuck in the fan
  2. Defective fan motor
  3. Defective outdoor unit PCB
  4. Fan motor connector disconnected

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch, then look through the outdoor unit's fan grille for leaves, ice, plastic bags or other debris
  • Clear away anything blocking the fan or the coil from outside the cabinet
  • Turn the power back on once after clearing the blockage

When to call a technician

If the fan is clear and E7 comes back, the outdoor fan motor or control board is at fault. Do not remove the fan guard or reach into the cabinet.

Sources

Daikin mini-split code E8: Input overcurrent detection

Soft lockout

Input overcurrent detection. Input current to the outdoor unit exceeded roughly 9.25 to 20 A for 2.5 seconds while the compressor was running (the trip point drops as outdoor temperature rises).

Manual wording: “E8 Input overcurrent detection”

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units

Likely causes, most common first

  1. Outdoor temperature is out of operation range
  2. Defective compressor
  3. Defective power module
  4. Defective outdoor unit PCB
  5. Short circuit

What you can safely check yourself

  • Check whether the outdoor temperature is far outside the unit's rated operating range
  • Check the outdoor unit has clear airflow and is not blocked by snow, leaves or a cover
  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

E8 means the unit is drawing more current than allowed. Measuring input current and checking the compressor windings requires a technician.

Sources

Daikin mini-split code E9: Moving part of electronic expansion valve

Soft lockout

Moving part of electronic expansion valve (Y1E, Y3E) abnormality. No current was detected through the expansion valve coil common line at power-up, so the control assumes the valve or its wiring is open.

Manual wording: “E9 Moving part of electronic expansion valve (Y1E, Y3E) abnormality”

Documented for: RMXS multi-split outdoor units

Likely causes, most common first

  1. Disconnection of connectors for electronic expansion valve Y1E or Y3E
  2. Defective moving part of electronic expansion valve
  3. Defective main PCB (A1P)

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once

When to call a technician

The expansion valve and its coil are inside the outdoor unit's refrigerant section. Only a technician should check the coil continuity or replace the valve.

Source

Daikin mini-split code EA: Four way valve abnormality

Soft lockout

Four way valve abnormality. The control compared the room sensor to the indoor coil sensor and found the unit is not actually producing the mode it is running in - the reversing valve appears stuck or miswired.

Manual wording: “EA FourWay valve abnormality”

Documented for: Heat pump pair systems: FTXS-L, H-Series, FTXM-W/V

Likely causes, most common first

  1. Disconnection of four way valve coil
  2. Defective four way valve, coil, or harness
  3. Defective outdoor unit PCB
  4. Defective thermistor
  5. Refrigerant shortage
  6. Water mixed in refrigerant
  7. Defective stop valve

What you can safely check yourself

  • Confirm the remote is actually set to the mode you expect (heat vs cool)
  • Check and replace the indoor unit air filters
  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

A stuck reversing valve is a sealed-system repair. A technician needs to check the valve coil and the refrigerant charge.

Sources

Daikin mini-split code F3: Discharge pipe temperature control

Soft lockout

Discharge pipe temperature control. The compressor discharge line got too hot (about 221 to 248F depending on model and speed) so the compressor stopped. It clears once the pipe cools back down.

Manual wording: “F3 Discharge pipe temperature control”

Documented for: FTXS-L, H-Series, FTXM-W/V, RMXS outdoor units

Likely causes, most common first

  1. Refrigerant shortage
  2. Defective discharge pipe thermistor (or outdoor heat exchanger / outdoor temperature thermistor)
  3. Defective electronic expansion valve or coil
  4. Defective four way valve
  5. Water mixed in refrigerant
  6. Defective stop valve
  7. Defective outdoor unit PCB

What you can safely check yourself

  • Check the outdoor unit is clear of leaves, snow and debris and has clearance around it
  • Check and replace the indoor unit air filters
  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

F3 is nearly always low refrigerant charge or a restriction. A technician has to check charge and the expansion valve - do not just keep resetting it.

Sources

Daikin mini-split code F6: On pair systems, high pressure control in cooling - the outdoor coil sensor went above about 140-149F so the unit cut back or halted

Warning

On pair systems, high pressure control in cooling - the outdoor coil sensor went above about 140-149F so the unit cut back or halted. On RMXS multi-split systems F6 instead means the system is overcharged with refrigerant.

Manual wording: “F6 High pressure control in cooling”

Documented for: FTXS-L, H-Series, FTXM-W/V pair systems; RMXS multi-split (refrigerant overcharged)

Likely causes, most common first

  1. The installation space is not large enough
  2. Dirty outdoor heat exchanger
  3. Defective outdoor fan motor
  4. Defective stop valve
  5. Defective electronic expansion valve or coil
  6. Defective outdoor heat exchanger thermistor
  7. Defective outdoor unit PCB
  8. Refrigerant overcharge (multi-split)

What you can safely check yourself

  • Check the outdoor coil is not blocked with dirt, cottonwood, leaves or grass clippings
  • Clear shrubs, fencing or stored items crowding the outdoor unit
  • Check the outdoor fan is running and not obstructed
  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

If the outdoor unit has clear airflow and a clean coil and F6 persists, a technician needs to check charge, the fan motor and the outdoor coil sensor.

Sources

Daikin mini-split code F8: System shutdown due to compressor internal temperature abnormality

Hard lockout

System shutdown due to compressor internal temperature abnormality. The discharge pipe thermistor exceeded 261.5F during forced cooling operation and the system shut itself down.

Manual wording: “F8 System shutdown due to compressor internal temperature abnormality”

Documented for: FTXM-W/V (Daikin Atmosphera)

Likely causes, most common first

  1. Abnormal operation due to air intrusion into the refrigerant circuit
  2. Defective discharge pipe thermistor
  3. Abnormal deformation of piping in the outdoor unit

What you can safely check yourself

  • Shut the system off at the breaker or disconnect switch and leave it off until a technician can look at it

When to call a technician

F8 is a shutdown, not a temporary trip - the manual's own path ends in replacing the discharge thermistor and PCB or the whole outdoor unit. Call a technician and do not keep resetting it.

Source

Daikin mini-split code H0: Compressor system sensor abnormality

Soft lockout

Compressor system sensor abnormality. Before the compressor starts, the DC current or DC voltage reading is out of range (current sensor output outside 0.5 to 4.5 V, or DC bus below 50 V), or the compressor draws no current at start-up.

Manual wording: “H0 Compressor system sensor abnormality”

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units

Likely causes, most common first

  1. Broken or disconnected harness
  2. Disconnection of the compressor harness
  3. Disconnection of reactor
  4. Defective outdoor unit PCB
  5. Defective compressor
  6. Supply voltage obviously low or high

What you can safely check yourself

  • Check the breaker or disconnect for the outdoor unit is fully on
  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once

When to call a technician

H0 means the outdoor board cannot see the compressor's current or voltage. Checking the reactor and compressor harness inside the outdoor electrical box is technician work.

Sources

Daikin mini-split code H6: Position sensor abnormality - the compressor failed to start

Soft lockout

Position sensor abnormality - the compressor failed to start. The position-detection circuit could not establish the compressor's rotor position at start-up.

Manual wording: “H6 Position sensor abnormality”

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units

Likely causes, most common first

  1. Start-up failure caused by the closed stop valve
  2. Input voltage is outside the specified range
  3. Disconnection of the compressor relay cable
  4. Defective compressor
  5. Defective outdoor unit PCB

What you can safely check yourself

  • Check the breaker or disconnect for the outdoor unit is fully on
  • Turn the system off at the breaker or disconnect switch, leave it off at least 30 seconds, and turn it back on once

When to call a technician

H6 needs supply voltage and discharge pressure measured at the outdoor unit. A closed stop valve left over from installation is a common cause and only a technician should open it.

Sources

Daikin mini-split code H8: DC voltage or current sensor abnormality on 09/12 class units, or CT

Soft lockout

DC voltage or current sensor abnormality on 09/12 class units, or CT (current transformer) or related abnormality on 24/30/36 class units. The compressor is running above about 32 Hz but the sensed input current is implausibly low.

Manual wording: “H8 DC voltage / current sensor abnormality (09/12 class only) / CT or related abnormality (24/30/36 class only)”

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units

Likely causes, most common first

  1. Defective outdoor unit PCB
  2. Defective power module
  3. Broken or disconnected wiring
  4. Defective reactor

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once

When to call a technician

The manual's own remedy for H8 is replacing the outdoor unit PCB after current measurements. That is a technician job.

Sources

Daikin mini-split code H9: Outdoor temperature thermistor or related abnormality

Warning

Outdoor temperature thermistor or related abnormality. The outdoor air temperature sensor is reading open or shorted (input voltage above 4.96 V or below 0.04 V).

Manual wording: “H9 Outdoor temperature thermistor or related abnormality”

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units, RMXS multi-split outdoor

Likely causes, most common first

  1. Disconnection of the connector for the thermistor
  2. Defective thermistor corresponding to the error code
  3. Defective outdoor unit PCB

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

The sensor and its connector are inside the outdoor unit. A technician has to check the thermistor's resistance and reseat or replace it.

Sources

Daikin mini-split code J3: Discharge pipe thermistor or related abnormality

Warning

Discharge pipe thermistor or related abnormality. The compressor discharge sensor is open or shorted, or it is reading colder than the heat exchanger, which is physically impossible.

Manual wording: “J3 Discharge pipe thermistor or related abnormality”

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units, RMXS multi-split outdoor

Likely causes, most common first

  1. Disconnection of the connector for the thermistor
  2. Defective discharge pipe thermistor
  3. Defective heat exchanger thermistor (outdoor coil in cooling, indoor coil in heating)
  4. Defective outdoor unit PCB

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

A discharge sensor that has slipped out of its holder or failed has to be reseated or replaced by a technician - running without it risks overheating the compressor.

Sources

Daikin mini-split code J5: Suction pipe thermistor

Warning

Suction pipe thermistor (R3T, R5T) abnormality. A short or open circuit was detected in the suction line temperature sensor.

Manual wording: “J5 Suction pipe thermistor (R3T, R5T) abnormality”

Documented for: RMXS multi-split outdoor units

Likely causes, most common first

  1. Disconnection of thermistor
  2. Defective suction pipe thermistor (R3T, R5T)
  3. Defective main PCB (A1P)

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

A technician must identify which of the two suction thermistors failed using the outdoor unit's monitor mode.

Source

Daikin mini-split code J6: Outdoor heat exchanger thermistor or related abnormality

Warning

Outdoor heat exchanger thermistor or related abnormality. The outdoor coil temperature sensor is reading open or shorted.

Manual wording: “J6 Outdoor heat exchanger thermistor or related abnormality”

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units, RMXS multi-split outdoor

Likely causes, most common first

  1. Disconnection of the connector for the thermistor
  2. Defective outdoor heat exchanger thermistor
  3. Defective outdoor unit PCB

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

The outdoor coil sensor drives defrost and high-pressure protection. A technician needs to check and replace it.

Sources

Daikin mini-split code J7: Outdoor liquid pipe thermistor

Warning

Outdoor liquid pipe thermistor (R7T) abnormality. A short or open circuit was detected in the outdoor liquid line temperature sensor.

Manual wording: “J7 Outdoor liquid pipe thermistor (R7T) abnormality”

Documented for: RMXS multi-split outdoor units

Likely causes, most common first

  1. Disconnection of thermistor
  2. Defective outdoor liquid pipe thermistor (R7T)
  3. Defective main PCB (A1P)

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

The sensor plugs into X13A on the outdoor main PCB - reconnecting or replacing it is technician work.

Source

Daikin mini-split code J8: Liquid pipe thermistor or related abnormality

Warning

Liquid pipe thermistor or related abnormality. The liquid line temperature sensor at the outdoor unit is reading open or shorted.

Manual wording: “J8 Liquid pipe thermistor or related abnormality”

Documented for: FTXM-W/V (Daikin Atmosphera) outdoor units

Likely causes, most common first

  1. Disconnection of the connector for the thermistor
  2. Defective thermistor
  3. Defective outdoor unit PCB

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

A technician has to check the thermistor's resistance and connector inside the outdoor unit.

Source

Daikin mini-split code J9: Subcooling heat exchanger gas pipe thermistor

Warning

Subcooling heat exchanger gas pipe thermistor (R6T) abnormality. That sensor read open or shorted.

Manual wording: “J9 Subcooling heat exchanger gas pipe thermistor (R6T) abnormality”

Documented for: RMXS multi-split outdoor units

Likely causes, most common first

  1. Disconnection of thermistor
  2. Defective subcooling heat exchanger gas pipe thermistor (R6T)
  3. Defective main PCB (A1P)

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

Sensor replacement inside the outdoor unit is a technician job.

Source

Daikin mini-split code JA: High pressure sensor abnormality

Warning

High pressure sensor abnormality. The outdoor unit's high-side pressure transducer is reading out of range.

Manual wording: “JA High pressure sensor abnormality”

Documented for: RMXS multi-split outdoor units

Likely causes, most common first

  1. Disconnection of the high pressure sensor connector
  2. Defective high pressure sensor
  3. Defective main PCB (A1P)

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

The pressure sensor is part of the sealed refrigerant circuit and must be diagnosed and replaced by a technician.

Source

Daikin mini-split code JC: Low pressure sensor abnormality

Warning

Low pressure sensor abnormality. The outdoor unit's low-side pressure transducer is reading out of range.

Manual wording: “JC Low pressure sensor abnormality”

Documented for: RMXS multi-split outdoor units

Likely causes, most common first

  1. Disconnection of the low pressure sensor connector
  2. Defective low pressure sensor
  3. Defective main PCB (A1P)

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

Same as JA - sealed-system sensor, technician only.

Source

Daikin mini-split code L1: Outdoor unit PCB abnormality on the inverter side

Hard lockout

Outdoor unit PCB abnormality on the inverter side. Overcurrent was detected during waveform output before the compressor started, or the current sensor misbehaved during synchronous start-up.

Manual wording: “L1 Outdoor unit PCB abnormality”

Documented for: RMXS multi-split outdoor units

Likely causes, most common first

  1. IPM (power module) failure
  2. Current sensor failure
  3. Failure of IGBT or drive circuit
  4. Defective main PCB (A1P)

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once

When to call a technician

L1 is an inverter power-section failure. It ends in an outdoor board replacement by a technician.

Source

Daikin mini-split code L3: Electrical box temperature rise

Soft lockout

Electrical box temperature rise. With the compressor off, the radiation fin sensor in the outdoor electrical box read too high (about 208 to 252F depending on class), so the control shut things down to protect the electronics.

Manual wording: “L3 Electrical box temperature rise”

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units

Likely causes, most common first

  1. Defective outdoor fan motor
  2. Short circuit (hot discharge air recirculating into the unit)
  3. Defective radiation fin thermistor
  4. Disconnection of connector
  5. Defective outdoor unit PCB

What you can safely check yourself

  • Check the outdoor unit has clear space around it and is not enclosed or crowded by fencing or plants
  • Check the outdoor coil is not blocked with debris
  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

If the outdoor unit has proper clearance and L3 persists, the outdoor fan motor, the fin thermistor or the board needs a technician.

Sources

Daikin mini-split code L4: Radiation fin temperature rise

Soft lockout

Radiation fin temperature rise. With the compressor running, the inverter heat sink got too hot (about 185 to 221F depending on class) and the unit stopped.

Manual wording: “L4 Radiation fin temperature rise”

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units, RMXS multi-split outdoor

Likely causes, most common first

  1. Defective outdoor fan motor
  2. Short circuit (hot air recirculating into the outdoor unit)
  3. Defective radiation fin thermistor
  4. Disconnection of connector
  5. Defective outdoor unit PCB
  6. Silicon grease not applied properly on the radiation fin after replacing the outdoor unit PCB

What you can safely check yourself

  • Check the outdoor unit is not enclosed, crowded or blowing its own hot air straight back into itself
  • Clear leaves, grass and debris from the outdoor coil and around the base
  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

If airflow around the outdoor unit is good and L4 keeps coming back, the fan motor or the inverter heat sink assembly needs a technician.

Sources

Daikin mini-split code L5: Output overcurrent detection

Hard lockout

Output overcurrent detection. The inverter's DC section saw an overcurrent, or the compressor position or speed signal went wrong while running, and the system shut down.

Manual wording: “L5 Output overcurrent detection”

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units, RMXS multi-split outdoor

Likely causes, most common first

  1. Poor installation condition
  2. Closed stop valve
  3. Defective power module
  4. Wrong internal wiring
  5. Abnormal power supply voltage
  6. Defective outdoor unit PCB
  7. Defective compressor

What you can safely check yourself

  • Check the outdoor unit has clear airflow and adequate clearance
  • Turn the system off at the breaker or disconnect switch, leave it off at least 30 seconds, and turn it back on once

When to call a technician

L5 usually means the compressor or the inverter power module is failing, or a stop valve was left closed. All of it is technician work.

Sources

Daikin mini-split code L8: Inverter current abnormality

Soft lockout

Inverter current abnormality. Inverter secondary current stayed at or above 19.0 A for 5 seconds, or at or above 16.1 A for 260 seconds - the compressor is overloaded.

Manual wording: “L8 Inverter current abnormality”

Documented for: RMXS multi-split outdoor units

Likely causes, most common first

  1. Compressor overload
  2. Compressor coil disconnected
  3. Defective main PCB (A1P)

What you can safely check yourself

  • Check the outdoor unit is clear of debris and has proper airflow
  • Check and replace the indoor unit air filters
  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

The manual's path is to inspect the compressor and refrigerant system and often replace the compressor. Technician only.

Source

Daikin mini-split code L9: Compressor start-up error

Soft lockout

Compressor start-up error. The compressor's starting control sequence never completed.

Manual wording: “L9 Compressor start-up error”

Documented for: RMXS multi-split outdoor units

Likely causes, most common first

  1. Large pressure difference before starting the compressor (unsatisfactory pressure equalization)
  2. Defective compressor
  3. Defective main PCB (A1P)

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch, leave it off a few minutes so pressures equalize, and turn it back on once

When to call a technician

If L9 repeats, a technician has to check the refrigerant system for a restriction and test the compressor.

Source

Daikin mini-split code P1: High voltage of capacitor in main inverter circuit

Soft lockout

High voltage of capacitor in main inverter circuit. The main circuit capacitor's voltage waveform looks like an open-phase power supply.

Manual wording: “P1 High voltage of capacitor in main inverter circuit”

Documented for: RMXS multi-split outdoor units

Likely causes, most common first

  1. Defective main circuit capacitor
  2. Improper main circuit wiring
  3. Defective main PCB (A1P)

What you can safely check yourself

  • Check both legs of the outdoor unit breaker are on and there has not been a partial power outage

When to call a technician

The main inverter capacitor stores dangerous voltage even after power is off. Only a technician should open the outdoor electrical box.

Source

Daikin mini-split code P4: Radiation fin thermistor or related abnormality

Warning

Radiation fin thermistor or related abnormality. The sensor that watches the inverter heat sink temperature is open or shorted.

Manual wording: “P4 Radiation fin thermistor or related abnormality”

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units, RMXS multi-split outdoor

Likely causes, most common first

  1. Defective radiation fin thermistor
  2. Defective outdoor unit PCB

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch and back on once

When to call a technician

On pair systems the fin thermistor is part of the outdoor PCB, so the manual's remedy for P4 is replacing the outdoor unit PCB. Technician only.

Sources

Daikin mini-split code U0: Refrigerant shortage

Warning

Refrigerant shortage. The control compared input current, compressor speed, discharge pipe temperature and expansion valve position and concluded the system is low on refrigerant. On RMXS multi-split systems it reads as low pressure drop due to refrigerant shortage or an expansion valve fault.

Manual wording: “U0 Refrigerant shortage”

Documented for: FTXS-L, FDXS-L, H-Series, FTXM-W/V, RMXS multi-split

Likely causes, most common first

  1. Refrigerant shortage (refrigerant leakage)
  2. Closed stop valve
  3. Disconnection of the discharge pipe, indoor or outdoor heat exchanger, room or outdoor temperature thermistor
  4. Poor compression performance of compressor
  5. Defective electronic expansion valve
  6. Refrigerant system clogging / incorrect piping (multi-split)

What you can safely check yourself

  • Check and replace the indoor unit air filters
  • Check the outdoor unit is clear of snow, leaves and debris
  • Note whether cooling or heating has been getting gradually weaker over weeks - that pattern points to a leak

When to call a technician

U0 means a technician needs to leak-check and weigh in charge. Topping off refrigerant without finding the leak is illegal to do yourself and just repeats the problem.

Sources

Daikin mini-split code U2: Low-voltage detection or over-voltage detection

Warning

Low-voltage detection or over-voltage detection. Either the indoor unit saw no zero-cross signal on its power supply for about 10 seconds, or the outdoor unit's DC bus dropped below roughly 150-200 V or spiked too high. The compressor stops and retries after a 3-minute standby.

Manual wording: “U2 Low-voltage detection or over-voltage detection”

Documented for: FTXS-L, FDXS-L, H-Series, FTXM-W/V, RMXS multi-split

Likely causes, most common first

  1. Supply voltage is not as specified
  2. Momentary fall of voltage
  3. Noise
  4. Disconnection of compressor harness
  5. Defective DC voltage detection circuit
  6. Defective over-voltage detection circuit
  7. Defective PAM control part

What you can safely check yourself

  • Check whether the house has had brownouts, flickering lights or a recent utility outage
  • Check the breaker or disconnect for the indoor and outdoor units is fully on
  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once

When to call a technician

If the incoming power is steady and U2 persists, the outdoor unit's voltage detection circuit or board is at fault and needs a technician. Measuring supply voltage at the terminal board is not a homeowner job.

Sources

Daikin mini-split code U3: Check operation is not conducted

Warning

Check operation is not conducted. The multi-zone system was started without the installer running the required commissioning check operation.

Manual wording: “U3 Check operation is not conducted”

Documented for: RMXS multi-split systems

Likely causes, most common first

  1. Check operation was never executed after installation

When to call a technician

This one is purely an installer step - the check operation is started from a button on the outdoor unit's service PCB. Call whoever installed the system.

Source

Daikin mini-split code U4: Signal transmission error between the indoor unit and the outdoor unit

Soft lockout

Signal transmission error between the indoor unit and the outdoor unit. The indoor unit either cannot receive data from the outdoor unit or the data it receives is corrupt.

Manual wording: “U4 Signal transmission error (between indoor unit and outdoor unit)”

Documented for: FTXS-L, FDXS-L, H-Series, FTXM-W/V pair systems; on RMXS, indoor unit to Branch Provider unit transmission

Likely causes, most common first

  1. Wiring error
  2. Breaking of the connection wires between the indoor and outdoor units (wire No. 3)
  3. Defective outdoor unit PCB
  4. Defective indoor unit PCB
  5. Disturbed power supply waveform

What you can safely check yourself

  • Check the breaker or disconnect for the outdoor unit is on - the indoor unit will report U4 if the outdoor unit has no power
  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once

When to call a technician

U4 is the most common Daikin mini-split code and it is almost always the interconnecting wiring or a board. Checking wire No. 3 and the terminal board voltages requires a technician.

Sources

Daikin mini-split code U5: Signal transmission error between the indoor unit and the remote controller

Warning

Signal transmission error between the indoor unit and the remote controller. Normal communication with the wired controller did not continue for the specified period.

Manual wording: “U5 Signal transmission error between indoor unit and remote controller”

Documented for: Systems with a wired wall remote controller

Likely causes, most common first

  1. Connection of two MAIN remote controllers when using two controllers
  2. Defective indoor unit PCB
  3. Defective remote controller
  4. Signal transmission error caused by noise

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once

When to call a technician

If two wall controllers are installed, one must be set to SUB - that dip switch setting and the controller wiring are a technician's job.

Source

Daikin mini-split code U7: Signal transmission error on the outdoor unit PCB

Soft lockout

Signal transmission error on the outdoor unit PCB. The main microcomputer stopped receiving data from the power module for 9 seconds.

Manual wording: “U7 Signal transmission error on outdoor unit PCB (24/30/36 class only)”

Documented for: FTXS-L and H-Series 24/30/36 class outdoor units

Likely causes, most common first

  1. Defective outdoor unit PCB
  2. External factor such as electrical noise

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once

When to call a technician

The manual's remedy if U7 returns after a power cycle is to replace the outdoor unit PCB. If it does not return, the manual says the cause was likely external and to keep an eye on it.

Sources

Daikin mini-split code U8: Signal transmission error between the MAIN remote controller and the SUB remote controller

Warning

Signal transmission error between the MAIN remote controller and the SUB remote controller.

Manual wording: “U8 Signal transmission error between MAIN remote controller and SUB remote controller”

Documented for: Systems with two wired wall remote controllers on one indoor unit

Likely causes, most common first

  1. Remote controller is set to SUB when only one controller is used
  2. Connection of two SUB remote controllers
  3. Defective remote controller PCB

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once

When to call a technician

The MAIN/SUB setting lives inside the wall controller. Have a technician set it correctly.

Source

Daikin mini-split code U9: Signal transmission error between an indoor unit and the outdoor unit within the same multi-zone system

Soft lockout

Signal transmission error between an indoor unit and the outdoor unit within the same multi-zone system. One zone's indoor unit or its expansion valve is faulting and taking the whole system's communication down.

Manual wording: “U9 Signal transmission error between indoor unit and outdoor unit in the same system”

Documented for: RMXS and other multi-zone systems

Likely causes, most common first

  1. Improper connection of transmission wiring between indoor and outdoor unit
  2. Defective indoor unit PCB in another zone
  3. Defective electronic expansion valve in an indoor unit of another zone

What you can safely check yourself

  • Turn every indoor unit on and note which zone shows the fault
  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once
  • Wait at least 2 minutes before reading the code again - the manual says a fresh U9 needs 2 minutes to settle

When to call a technician

U9 points to a different zone than the one showing the code. Tracing which indoor unit is at fault across a multi-zone system is a technician's job.

Source

Daikin mini-split code UA: On pair systems, unspecified voltage between indoor and outdoor unit - a pair-type and a multi-type unit have been connected together

Soft lockout

On pair systems, unspecified voltage between indoor and outdoor unit - a pair-type and a multi-type unit have been connected together. On multi-zone systems the same code means mismatching of indoor and outdoor units or too many indoor units connected.

Manual wording: “UA Unspecified voltage (between indoor unit and outdoor unit)”

Documented for: All Daikin residential ductless; meaning differs between pair and multi-zone platforms

Likely causes, most common first

  1. Wrong models interconnected
  2. Wrong wiring of connecting wires
  3. Wrong indoor unit PCB or outdoor unit PCB mounted
  4. Defective indoor unit PCB
  5. Defective outdoor unit PCB
  6. Excess of connected indoor units (multi-zone)
  7. Mismatching of the refrigerant type of indoor and outdoor unit (multi-zone)
  8. Outdoor unit PCB setting not performed after replacing with a spare parts PCB (multi-zone)

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once

When to call a technician

UA is essentially an installation or parts-compatibility problem. Whoever installed or last serviced the system needs to verify the indoor/outdoor combination and the wiring.

Sources

Daikin mini-split code UC: Address duplication of central remote controller

Warning

Address duplication of central remote controller. Two indoor units on the network were assigned the same centralized address.

Manual wording: “UC Address duplication of central remote controller”

Documented for: Systems using centralized control

Likely causes, most common first

  1. Address duplication of centralized remote controller
  2. Defective indoor unit PCB

When to call a technician

Addressing is set in the field by the installer. A technician has to change one unit's centralized address.

Source

Daikin mini-split code UE: Transmission error between the centralized remote controller and an indoor unit

Warning

Transmission error between the centralized remote controller and an indoor unit. Communication with the central controller stopped for a set period.

Manual wording: “UE Transmission error between centralized remote controller and indoor unit”

Documented for: Systems using centralized control

Likely causes, most common first

  1. Transmission error between optional controllers for centralized control and the indoor unit
  2. Connector for setting master controller is disconnected
  3. Defective PCB of centralized remote controller
  4. Defective indoor unit PCB

What you can safely check yourself

  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once

When to call a technician

The manual's step is to reset power to all centralized controllers simultaneously and check the master-controller connector. Leave that to a technician.

Source

Daikin mini-split code UF: System is not set yet

Soft lockout

System is not set yet. During the check operation, the number of indoor units communicating did not match the number that actually changed temperature - meaning the refrigerant piping and the wiring do not run to the same zones.

Manual wording: “UF System is not set yet”

Documented for: RMXS and other multi-zone systems

Likely causes, most common first

  1. Stop valve is left closed
  2. Improper connection of transmission wiring between indoor unit and outdoor unit
  3. Failure to execute check operation
  4. Defective indoor unit PCB

When to call a technician

UF means the installation is crossed or incomplete - piping to one zone with wiring to another, or stop valves still closed. This has to go back to the installer.

Source

Daikin mini-split code UH: System abnormality, refrigerant system address undefined

Soft lockout

System abnormality, refrigerant system address undefined. The outdoor unit found an indoor unit that never got an auto-assigned address.

Manual wording: “UH System abnormality, refrigerant system address undefined”

Documented for: RMXS and other multi-zone systems

Likely causes, most common first

  1. Improper connection of transmission wiring between indoor and outdoor unit
  2. Defective indoor unit PCB
  3. Defective main PCB (A1P)

What you can safely check yourself

  • If the system was just powered up for the first time, allow at least 12 minutes for auto-addressing before reading the code again

When to call a technician

If UH is still there after auto-addressing has had time to finish, a technician has to trace the transmission wiring between the indoor units and the outdoor unit.

Source

Daikin mini-split Operation Lamp Blinking: The green OPERATION lamp on the face of the indoor unit blinks when the unit has detected a fault

WarningShown as: Green OPERATION lamp on the indoor unit blinking continuously

The green OPERATION lamp on the face of the indoor unit blinks when the unit has detected a fault. Per the service manual it blinks in exactly two situations: a protection device in the indoor or outdoor unit has activated or a thermistor has malfunctioned, or a signal transmission error has occurred between the indoor and outdoor units. The lamp does not tell you which fault - you have to read the actual code from the remote using the service-check procedure.

Manual wording: “The operation lamp blinks when any of the following errors is detected. 1. When a protection device of the indoor or outdoor unit is activated, or when the thermistor malfunctions. 2. When a signal transmission error occurs between the indoor and outdoor units.”

Documented for: FTXS series and FDXS series indoor units; the same green OPERATION lamp behavior applies across Daikin residential ductless indoor units

Likely causes, most common first

  1. A protection device of the indoor or outdoor unit is activated
  2. A thermistor (temperature sensor) malfunction
  3. A signal transmission error between the indoor and outdoor units

What you can safely check yourself

  • Check and replace the indoor unit air filters
  • Make sure indoor airflow and the outdoor unit are not blocked
  • Check the breaker or disconnect for both the indoor and outdoor unit is fully on
  • Retrieve the actual error code: hold the remote's TIMER CANCEL button for 5 seconds, then press it repeatedly until you hear a long beep - the two characters shown are the code

When to call a technician

A blinking green lamp always has a stored code behind it. Read the code first, then call a technician with that code in hand.

Source

How old is this Daikin?

Age changes what a fault code means for you. The same failure is a routine repair on a six-year-old unit and the end of the line on a twenty-year-old one. Your Daikin serial number has the build date in it.

Decode your Daikinserial number →

Manuals used for this page