HVAC Code Lookup

LG fault codes

48 documented codes for LG mini-splits, each cited to the manufacturer's own manual. LG uses one CH## error-code set across its residential ductless line: single-zone wall-mount (LS/LA/LAN indoor + LSU/LAU outdoor), Art Cool, ceiling cassette, ducted/LGRED, and the Multi F / Multi F MAX multi-zone systems (LMU outdoor units). CH01-CH12 are indoor-unit faults and CH21-CH73 are outdoor-unit faults, except CH05/CH53 which are the two ends of the same indoor-to-outdoor communication fault. LG's commercial Multi V VRF equipment uses the same low numbers plus a much larger extended code set that is NOT covered here..

Mini-Split codes

CodeMeaningSeverity
CH00No errorStatus
CH01Indoor unit LED1 (units place) blinks 1 timeIndoor unit roomSoft lockout
CH02Indoor unit LED1 (units place) blinks 2 timesIndoor unit inlet pipe sensor errorSoft lockout
CH03Indoor unit LED1 (units place) blinks 3 timesWired remote controllerSoft lockout
CH04Indoor unit LED1 (units place) blinks 4 timesDrain pump / float switch errorSoft lockout
CH05Indoor unit LED1 (units place) blinks 5 timesCommunication error between the indoor unit and the outdoor unitSoft lockout
CH06Indoor unit LED1 (units place) blinks 6 timesIndoor unit outlet pipe sensor errorSoft lockout
CH07Indoor unit LED1 (units place) blinks 7 timesDifferent mode operation errorWarning
CH09Indoor unit LED1 (units place) blinks 9 timesIndoor unit EEPROM errorHard lockout
CH10Indoor unit LED2 (tens place) blinks 1 time, LED1 does not blinkIndoor unit BLDC fan motor lockSoft lockout
CH12Indoor unit LED1 (units place) blinks 2 times and LED2 (tens place) blinks 1 timeIndoor unit middle pipe sensor errorSoft lockout
CH21Outdoor LED01 (red) blinks 2 times, LED02 (green) blinks 1 timeDC Peak / IPM faultHard lockout
CH22Outdoor LED01 (red) blinks 2 times, LED02 (green) blinks 2 timesCT2Soft lockout
CH23Outdoor LED01 (red) blinks 2 times, LED02 (green) blinks 3 timesDC link voltage error - the DC bus inside the inverter has dropped below about 140 VDC or risen above about 420 VDCSoft lockout
CH24Outdoor LED1 blinks 2 times, LED2 blinks 4 timesPressure switch / heat sink protection has trippedHard lockout
CH25Outdoor LED01 (red) blinks 2 times, LED02 (green) blinks 5 timesAC low / high voltageSoft lockout
CH26Outdoor LED01 (red) blinks 2 times, LED02 (green) blinks 6 timesDC compressor position errorHard lockout
CH27Outdoor LED01 (red) blinks 2 times, LED02 (green) blinks 7 timesPSC / PFC fault - overcurrent in the power factor correction stage between the AC input and the DC converter circuit of the inverter boardHard lockout
CH28Outdoor LED1 blinks 2 times, LED2 blinks 8 timesInverter compressor DC voltage is too highSoft lockout
CH29Outdoor LED01 (red) blinks 2 times, LED02 (green) blinks 9 timesCompressor phase overcurrent - the current into the compressor windings is higher than allowedHard lockout
CH31Outdoor LED1 blinks 3 times, LED2 blinks 1 timeCurrent transformerSoft lockout
CH32Outdoor LED01 (red) blinks 3 times, LED02 (green) blinks 2 timesInverter compressor discharge pipeSoft lockout
CH34Outdoor LED1 blinks 3 times, LED2 blinks 4 times (2-LED type; the service manual pairs CH34 with CH35 in one row)High pressure sensor errorSoft lockout
CH35Outdoor LED01 (red) blinks 3 times, LED02 (green) blinks 5 timesLow pressure error - suction pressure has dropped below the recommended limitSoft lockout
CH36Outdoor LED1 blinks 3 times, LED2 blinks 6 times (2-LED type; service manual lists this row as '36 (38)')Refrigerant leakage detectionHard lockout
CH37Outdoor LED1 blinks 3 times, LED2 blinks 7 times (2-LED type)Compression ratio limit exceededSoft lockout
CH38Outdoor LED1 blinks 3 times, LED2 blinks 6 times (2-LED type; service manual lists this row as '36 (38)')Refrigerant leakage detection - the system is low on refrigerantHard lockout
CH39Outdoor LED01 (red) blinks 3 times, LED02 (green) blinks 9 timesCommunication error between the PFC MICOM and the inverter MICOM - the two microcontrollers on the outdoor unit's power board have lost contact with each otherSoft lockout
CH40Outdoor LED01 (red) blinks 4 times, LED02 (green) does not blinkCurrent transformerHard lockout
CH41Outdoor LED01 (red) blinks 4 times, LED02 (green) blinks 1 timeInverter compressor discharge pipeSoft lockout
CH42Outdoor LED1 blinks 4 times, LED2 blinks 2 times (2-LED type)Low pressure sensor open or shortSoft lockout
CH43Outdoor LED01 (red) blinks 4 times, LED02 (green) blinks 3 timesHigh pressure sensor is disconnected or shorted outSoft lockout
CH44Outdoor LED01 (red) blinks 4 times, LED02 (green) blinks 4 timesOutdoor airSoft lockout
CH45Outdoor LED01 (red) blinks 4 times, LED02 (green) blinks 5 timesMid-pipe thermistor of the outdoor unit condenser coil is disconnected or shorted outSoft lockout
CH46Outdoor LED01 (red) blinks 4 times, LED02 (green) blinks 6 timesOutdoor unit suction pipe thermistor is disconnected or shorted outSoft lockout
CH48Outdoor LED01 (red) blinks 4 times, LED02 (green) blinks 8 timesOutdoor unit condenser coil outletSoft lockout
CH51Outdoor LED01 (red) blinks 5 times, LED02 (green) blinks 1 timeOver capacity / combination ratio out of rangeHard lockout
CH53Outdoor LED01 (red) blinks 5 times, LED02 (green) blinks 3 timesCommunication failure from the outdoor unit to the indoor unitSoft lockout
CH54Outdoor LED01 (red) blinks 5 times, LED02 (green) blinks 4 timesOpen phase / reverse phase error - the outdoor unit's incoming power is missing a leg or wired in the wrong orderHard lockout
CH60Outdoor LED01 (red) blinks 6 times, LED02 (green) does not blinkOutdoor unit PCB EEPROM check sum errorHard lockout
CH61Outdoor LED01 (red) blinks 6 times, LED02 (green) blinks 1 timeOutdoor unit condenser coil pipe temperature is too highSoft lockout
CH62Outdoor LED01 (red) blinks 6 times, LED02 (green) blinks 2 timesOutdoor unit inverter compressor PCB heat sink temperature is too highSoft lockout
CH63Outdoor LED1 blinks 6 times, LED2 blinks 3 timesCondenser coil pipe thermistor temperature is too lowSoft lockout
CH65Outdoor LED01 (red) blinks 6 times, LED02 (green) blinks 5 timesHeat sink thermistor is disconnected or shorted outSoft lockout
CH67Outdoor LED01 (red) blinks 6 times, LED02 (green) blinks 7 timesOutdoor BLDC fan motor lock errorHard lockout
CH72Outdoor LED1 blinks 7 times, LED2 blinks 2 times (2-LED type)Four-waySoft lockout
CH73Outdoor LED01 (red) blinks 7 times, LED02 (green) blinks 3 timesPSC / PFC overcurrent error detected in software - the outdoor unit's power factor correction stage saw a current peak beyond its limitSoft lockout
CH93Indoor / outdoor unit communication errorSoft lockout

Looking it up by flash count?

If you counted LED flashes rather than reading a code number, start here:

Manuals used for this page