Daikin Mini-Split Code H0

Soft lockout

Compressor system sensor abnormality. Before the compressor starts, the DC current or DC voltage reading is out of range (current sensor output outside 0.5 to 4.5 V, or DC bus below 50 V), or the compressor draws no current at start-up.

Manual wording: “H0 Compressor system sensor abnormality

Documented for: RKS/RXS pair outdoor units, FTXM-W/V outdoor units

Likely causes, most common first

  1. Broken or disconnected harness
  2. Disconnection of the compressor harness
  3. Disconnection of reactor
  4. Defective outdoor unit PCB
  5. Defective compressor
  6. Supply voltage obviously low or high

What you can safely check yourself

  • Check the breaker or disconnect for the outdoor unit is fully on
  • Turn the system off at the breaker or disconnect switch, wait a minute, and turn it back on once

When to call a technician

H0 means the outdoor board cannot see the compressor's current or voltage. Checking the reactor and compressor harness inside the outdoor electrical box is technician work.

A Daikin mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.