Bryant Furnace: 1 Flashes
A Bryant furnace LED pattern starting with 1 flashes matches 8 documented codes: 10.1, 12.1, 13.1, 14.1, 14.2, 14.3, 15.1, 19.1. Watch the full pattern (short vs. long flashes) to tell them apart — all 8 are explained below.
Code 10.1: L1 polarity fault
L1 polarity fault. The polarity of the incoming 115 V power is reversed, so the control cannot prove flame and the furnace will not run.
Manual wording: “10.1 L1 POLARITY FAULT Rapid flash LED”
Documented for: 926TC, 912SE
Likely causes, most common first
- Line voltage hot and neutral reversed at a junction box, outlet or the furnace
- On twinned furnaces, incorrect low-voltage (24 V) transformer phasing
When to call a technician
Correcting reversed 115 V polarity means working inside live junction boxes. Call a licensed HVAC technician or electrician.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
- Installation, Start-up, Operating and Service and Maintenance Instructions - 912SE (Bryant Heating & Cooling Systems, 912SE Legacy Line 92% single-stage condensing gas furnace) · checked 2026-08-25
Code 12.1: "W" on at power up - normal operation
"W" on at power up - normal operation. The blower runs for 90 seconds because the furnace was powered up during a call for heat, or the call ended during the blower on-delay.
Manual wording: “12.1 "W" ON at power up - Normal operation. Blower runs for 90 seconds, if unit is powered up during a call for het (R-W closed)”
Documented for: 926TC, 912SE
Likely causes, most common first
- Power was interrupted and restored while the thermostat was calling for heat
- The thermostat call ended during the blower on-delay period
What you can safely check yourself
- Nothing to fix - this is normal after a power blip or after switching the furnace back on
When to call a technician
If 12.1 appears repeatedly without any power outages, have a technician check for a loose 115 V connection or a failing blower door switch.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
- Installation, Start-up, Operating and Service and Maintenance Instructions - 912SE (Bryant Heating & Cooling Systems, 912SE Legacy Line 92% single-stage condensing gas furnace) · checked 2026-08-25
Code 13.1: Limit circuit lockout
Limit circuit lockout. The limit, draft safeguard, flame rollout, or blocked-vent switch has been open longer than 3 minutes. The control locks out and auto-resets after 3 hours.
Manual wording: “13.1 LIMIT CIRCUIT LOCKOUT - Lockout occurs if the limit, draft safeguard, flame rollout, or blocked vent switch*(if used) is open longer than 3 minutes. Control will auto-reset after 3 hours. See code 33.”
Documented for: 926TC, 912SE
Likely causes, most common first
- Sustained overheating from restricted airflow - see code 33 for the full cause list
- Flame rollout switch tripped (requires manual reset by a technician)
- Defective limit switch or connections
What you can safely check yourself
- Check and replace a dirty air filter
- Make sure supply registers and return grilles are open and not blocked
- Make sure the furnace blower door is fully closed and latched
When to call a technician
A 3-minute limit trip means the furnace was genuinely overheating or not venting. Have a technician confirm why before running it again - a tripped flame rollout switch in particular must never be reset without finding the cause.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
- Installation, Start-up, Operating and Service and Maintenance Instructions - 912SE (Bryant Heating & Cooling Systems, 912SE Legacy Line 92% single-stage condensing gas furnace) · checked 2026-08-25
Code 14.1: Ignition lockout
Ignition lockout. The furnace failed to ignite the gas and prove flame in four attempts. The control auto-resets after 3 hours.
Manual wording: “14.1 IGNITION LOCKOUT - System failed to ignite gas and prove flame in 4 attempts. Control will auto-reset after 3 hours. See status code 34.”
Documented for: 926TC, 912SE
Likely causes, most common first
- Incorrect manifold pressure or gas firing rate
- Gas inlet pressure fluctuations
- Igniter, flame sensor, or gas valve problem - see code 34
What you can safely check yourself
- Check that other gas appliances in the house still work, confirming gas service is on
- Turn the furnace off at the service switch for a minute and back on once to allow one clean retry
When to call a technician
Everything on the ignition side - igniter, flame sensor, gas valve, gas pressure - is inside the burner compartment of a live gas appliance. Call a technician rather than opening it.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
- Installation, Start-up, Operating and Service and Maintenance Instructions - 912SE (Bryant Heating & Cooling Systems, 912SE Legacy Line 92% single-stage condensing gas furnace) · checked 2026-08-25
Code 14.2: Flame lost - the flame signal dropped out three times after 70 seconds of heating
Flame lost - the flame signal dropped out three times after 70 seconds of heating.
Manual wording: “14.2 FLAME LOST - 3 times after 70s of heating”
Documented for: 926TC, 912SE
Likely causes, most common first
- Incorrect manifold pressure and gas firing rate
- Gas inlet pressure fluctuations
- Flame sensing problem - see code 34
What you can safely check yourself
- Check that the air filter is clean and vents are open, since poor airflow can disturb the flame
When to call a technician
Repeated loss of an established flame is a combustion fault. Have a technician verify gas pressure and the flame sensing circuit before the furnace runs again.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
- Installation, Start-up, Operating and Service and Maintenance Instructions - 912SE (Bryant Heating & Cooling Systems, 912SE Legacy Line 92% single-stage condensing gas furnace) · checked 2026-08-25
Code 14.3: Lockout after seven loss-of-flame events during a single heat request
Lockout after seven loss-of-flame events during a single heat request.
Manual wording: “14.3 LOCKOUT - 7 loss of flame events during a heat request”
Documented for: 926TC, 912SE
Likely causes, most common first
- Incorrect manifold pressure and gas firing rate
- Gas inlet pressure fluctuations
- Flame sensing problem - see code 34
What you can safely check yourself
- Check that the air filter is clean and supply and return vents are open
When to call a technician
Do not keep resetting the furnace to force it to run. Seven flame losses in one call needs a technician to check gas supply and combustion setup.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
- Installation, Start-up, Operating and Service and Maintenance Instructions - 912SE (Bryant Heating & Cooling Systems, 912SE Legacy Line 92% single-stage condensing gas furnace) · checked 2026-08-25
Code 15.1: Blower RPM lockout
Blower RPM lockout. The control locked out because no blower RPM was detected.
Manual wording: “15.1 BLOWER RPM LOCKOUT - Lockout occurs when no blower rpm is detected.”
Documented for: 926TC
Likely causes, most common first
- Loose blower wire connections
- Failed blower motor
What you can safely check yourself
- Make sure the blower access door is fully closed and latched - the door switch cuts power to the blower
When to call a technician
Testing an ECM blower motor and its harness requires a technician with the right meter and the motor's specifications.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25
Code 19.1: InteliSense communication loss - the furnace control has lost communication with the ecobee for Bryant thermostat
InteliSense communication loss - the furnace control has lost communication with the ecobee for Bryant thermostat.
Manual wording: “19.1 INTELISENSE COMMUNICATION LOSS - Loss of InteliSense communications with the thermostat.”
Documented for: 926TC
Likely causes, most common first
- Loose or broken R and Y wire connections between the control and the thermostat
- Thermostat not configured for InteliSense
What you can safely check yourself
- Check that your thermostat still powers on and responds
- Check the thermostat's batteries if it uses them
When to call a technician
The thermostat wiring and InteliSense configuration should be checked by the dealer who set the system up.
A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Installation, Start-up, Operating and Service and Maintenance Instructions - 926TC (Bryant Heating & Cooling Systems, 926TC Preferred Series two-stage, variable-speed ECM multipoise condensing gas furnace) · checked 2026-08-25