LG Mini-Split: 6 Flashes
A LG mini-split LED pattern starting with 6 flashes matches 7 documented codes: CH06, CH60, CH61, CH62, CH63, CH65, CH67. Watch the full pattern (short vs. long flashes) to tell them apart — all 7 are explained below.
Code CH06: Indoor unit outlet pipe sensor error
Indoor unit outlet pipe sensor error. The thermistor on the indoor coil's outlet (gas side) refrigerant pipe is disconnected, shorted or open.
Manual wording: “Indoor unit outlet pipe temperature sensor is disconnected, shorted, or opened.”
Documented for: All LG residential mini-split indoor units
Likely causes, most common first
- Sensor mis-wiring or short at the connector
- Moisture penetration into the sensor
- Bad sensor canning sheath (damaged sensor sheath or insulation)
- Sensor housing removed so the sensor is off the pipe
- Indoor unit PCB fault (only after the sensor itself checks good)
What you can safely check yourself
- Turn the system off at the breaker for one minute, then back on, to see if the code clears
- Check that the indoor unit's front panel and filter access door are fully closed and latched
When to call a technician
The sensor sits on the refrigerant piping inside the indoor unit. Replacing it is a technician job.
A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Single Zone Four-Way Ceiling-Cassette Installation Manual (LG Electronics U.S.A., Inc., Single-zone four-way ceiling cassette indoor units with LUU090HV through LUU420HV outdoor units) · checked 2026-08-25
- MULTI F / MULTI F MAX Outdoor Unit Installation Manual (LG Electronics U.S.A., Inc., Multi F and Multi F MAX multi-zone heat pump outdoor units (LMU series) with standard wall-mount, Art Cool, cassette and ducted indoor units) · checked 2026-08-25
- Convertible Mid-Static Ducted LGRED Degree System Installation Manual (LG Electronics U.S.A., Inc., LGRED single-zone convertible mid-static ducted indoor units with LUU180HHV / LUU240HHV outdoor units) · checked 2026-08-25
- Defining Common Error Codes - Standard Wall-Mounted High-Efficiency Single Zone Systems (LG Electronics U.S.A. - Commercial Air Conditioning, LS091HSV and LS121HSV systems (LSN091HSV / LSN121HSV indoor units, LSU091HSV / LSU121HSV outdoor units)) · checked 2026-08-25
- Room Air Conditioner SVC Manual (General) - Trouble Shooting Guide with Error Code (LG Electronics, All LG single-zone room air conditioner / mini-split chassis (SW, SB, SC, S4, S5, SH, SA, SJ, SK)) · checked 2026-08-25
Code CH60: Outdoor unit PCB EEPROM check sum error
Outdoor unit PCB EEPROM check sum error. The memory chip on the outdoor control board that stores the unit's identity and factory parameters failed its integrity check.
Manual wording: “Outdoor unit printed circuit board (PCB) EEPROM check sum error”
Documented for: All LG residential mini-split outdoor units
What you can safely check yourself
- Turn the system off at the breaker for three minutes and back on
When to call a technician
A failed EEPROM checksum means the outdoor control board cannot trust its own configuration. A technician has to replace the board.
A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- MULTI F / MULTI F MAX Outdoor Unit Installation Manual (LG Electronics U.S.A., Inc., Multi F and Multi F MAX multi-zone heat pump outdoor units (LMU series) with standard wall-mount, Art Cool, cassette and ducted indoor units) · checked 2026-08-25
- Single Zone Four-Way Ceiling-Cassette Installation Manual (LG Electronics U.S.A., Inc., Single-zone four-way ceiling cassette indoor units with LUU090HV through LUU420HV outdoor units) · checked 2026-08-25
- Convertible Mid-Static Ducted LGRED Degree System Installation Manual (LG Electronics U.S.A., Inc., LGRED single-zone convertible mid-static ducted indoor units with LUU180HHV / LUU240HHV outdoor units) · checked 2026-08-25
- Defining Common Error Codes - Standard Wall-Mounted High-Efficiency Single Zone Systems (LG Electronics U.S.A. - Commercial Air Conditioning, LS091HSV and LS121HSV systems (LSN091HSV / LSN121HSV indoor units, LSU091HSV / LSU121HSV outdoor units)) · checked 2026-08-25
Code CH61: Outdoor unit condenser coil pipe temperature is too high
Outdoor unit condenser coil pipe temperature is too high. In cooling this means the outdoor unit is overheating; in heating it means the indoor coil is overheating. In both cases the system cannot get rid of the heat it is making.
Manual wording: “Condenser coil thermistor temperature is too high”
Documented for: All LG residential mini-split outdoor units
Likely causes, most common first
- Overload operation - indoor or outdoor fan restricted, screened, or blocked
- Heat exchanger (coil) contaminated with dirt, lint, cottonwood, or grass clippings
- Poor condenser pipe sensor assembly or burned sensor
- EEV connector displaced or poor EEV assembly
- Refrigerant overcharged
What you can safely check yourself
- Clear leaves, grass clippings, cottonwood, snow, or debris away from the outdoor coil and fan
- Remove anything stacked against or on top of the outdoor unit, and check there is clear space all around it
- Check and clean the indoor air filters
- Make sure the indoor supply and return grilles are open and unblocked
- Let the unit cool, then turn it off at the breaker for three minutes and back on
When to call a technician
If airflow is clear on both units and CH61 returns, the coil needs a proper cleaning or the charge and expansion valve need checking. Call a technician.
A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- MULTI F / MULTI F MAX Outdoor Unit Installation Manual (LG Electronics U.S.A., Inc., Multi F and Multi F MAX multi-zone heat pump outdoor units (LMU series) with standard wall-mount, Art Cool, cassette and ducted indoor units) · checked 2026-08-25
- Single Zone Four-Way Ceiling-Cassette Installation Manual (LG Electronics U.S.A., Inc., Single-zone four-way ceiling cassette indoor units with LUU090HV through LUU420HV outdoor units) · checked 2026-08-25
- Convertible Mid-Static Ducted LGRED Degree System Installation Manual (LG Electronics U.S.A., Inc., LGRED single-zone convertible mid-static ducted indoor units with LUU180HHV / LUU240HHV outdoor units) · checked 2026-08-25
- Defining Common Error Codes - Standard Wall-Mounted High-Efficiency Single Zone Systems (LG Electronics U.S.A. - Commercial Air Conditioning, LS091HSV and LS121HSV systems (LSN091HSV / LSN121HSV indoor units, LSU091HSV / LSU121HSV outdoor units)) · checked 2026-08-25
- Room Air Conditioner SVC Manual (General) - Trouble Shooting Guide with Error Code (LG Electronics, All LG single-zone room air conditioner / mini-split chassis (SW, SB, SC, S4, S5, SH, SA, SJ, SK)) · checked 2026-08-25
- LG Air Conditioner - Guide to Error Codes (LG USA Support help library) (LG Electronics U.S.A., Inc., LG residential single-split and multi-split air conditioners / heat pumps) · checked 2026-08-25
Code CH62: Outdoor unit inverter compressor PCB heat sink temperature is too high
Outdoor unit inverter compressor PCB heat sink temperature is too high. The aluminium heat sink that cools the inverter power module is overheating, usually because the outdoor unit is in a hot, cramped spot or its airflow is blocked.
Manual wording: “Outdoor unit inverter compressor PCB heat sink temperature is too high”
Documented for: All LG residential mini-split outdoor units
Likely causes, most common first
- Improper installation environment (outdoor unit in a tight, unventilated location)
- Overload operation - outdoor fan restricted, screened, or blocked
- Poor PCB heat sink assembly (heat sink not making good contact)
- Poor PCB temperature sensing circuit parts
What you can safely check yourself
- Clear leaves, grass clippings, snow, or debris away from the outdoor coil and fan
- Remove anything stacked against or on top of the outdoor unit and give it clear space on all sides
- Check nothing is blowing hot exhaust (dryer vent, another condenser) into the outdoor unit
- Let the unit cool, then turn it off at the breaker for three minutes and back on
When to call a technician
If the outdoor unit has clear airflow and CH62 returns, the heat sink mounting or its sensor is at fault and needs a technician. If the unit is genuinely in too tight a space, it may need relocating.
A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- MULTI F / MULTI F MAX Outdoor Unit Installation Manual (LG Electronics U.S.A., Inc., Multi F and Multi F MAX multi-zone heat pump outdoor units (LMU series) with standard wall-mount, Art Cool, cassette and ducted indoor units) · checked 2026-08-25
- Single Zone Four-Way Ceiling-Cassette Installation Manual (LG Electronics U.S.A., Inc., Single-zone four-way ceiling cassette indoor units with LUU090HV through LUU420HV outdoor units) · checked 2026-08-25
- Convertible Mid-Static Ducted LGRED Degree System Installation Manual (LG Electronics U.S.A., Inc., LGRED single-zone convertible mid-static ducted indoor units with LUU180HHV / LUU240HHV outdoor units) · checked 2026-08-25
- Defining Common Error Codes - Standard Wall-Mounted High-Efficiency Single Zone Systems (LG Electronics U.S.A. - Commercial Air Conditioning, LS091HSV and LS121HSV systems (LSN091HSV / LSN121HSV indoor units, LSU091HSV / LSU121HSV outdoor units)) · checked 2026-08-25
- Room Air Conditioner SVC Manual (General) - Trouble Shooting Guide with Error Code (LG Electronics, All LG single-zone room air conditioner / mini-split chassis (SW, SB, SC, S4, S5, SH, SA, SJ, SK)) · checked 2026-08-25
Code CH63: Condenser coil pipe thermistor temperature is too low
Condenser coil pipe thermistor temperature is too low. In heating mode this typically means the outdoor coil is icing or the system is not absorbing heat.
Manual wording: “Condenser coil pipe thermistor temperature is too low.”
Documented for: LS091HSV / LS121HSV systems (LSU091HSV / LSU121HSV outdoor units)
What you can safely check yourself
- Clear snow and ice away from around, under, and on top of the outdoor unit
- Make sure the outdoor unit is not sitting in a drift or a spot where roof runoff pours onto it
- Check and clean the indoor air filters
When to call a technician
If the outdoor unit is clear of snow and CH63 returns, the defrost system, charge, or the coil sensor needs a technician. Do not chip ice off the coil - the fins and refrigerant tubing damage easily.
A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Defining Common Error Codes - Standard Wall-Mounted High-Efficiency Single Zone Systems (LG Electronics U.S.A. - Commercial Air Conditioning, LS091HSV and LS121HSV systems (LSN091HSV / LSN121HSV indoor units, LSU091HSV / LSU121HSV outdoor units)) · checked 2026-08-25
Code CH65: Heat sink thermistor is disconnected or shorted out
Heat sink thermistor is disconnected or shorted out. The sensor that monitors the inverter power module's heat sink is not reporting.
Manual wording: “Heat sink thermistor is disconnected or has shorted out”
Documented for: All LG residential mini-split outdoor units
Likely causes, most common first
- Sensor mis-wiring or short at the connector
- Moisture penetration into the sensor or bad canning sheath on the sensor wire
What you can safely check yourself
- Turn the system off at the breaker for three minutes and back on
When to call a technician
The heat sink sensor sits on the live inverter board assembly. Technician only.
A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- MULTI F / MULTI F MAX Outdoor Unit Installation Manual (LG Electronics U.S.A., Inc., Multi F and Multi F MAX multi-zone heat pump outdoor units (LMU series) with standard wall-mount, Art Cool, cassette and ducted indoor units) · checked 2026-08-25
- Single Zone Four-Way Ceiling-Cassette Installation Manual (LG Electronics U.S.A., Inc., Single-zone four-way ceiling cassette indoor units with LUU090HV through LUU420HV outdoor units) · checked 2026-08-25
- Convertible Mid-Static Ducted LGRED Degree System Installation Manual (LG Electronics U.S.A., Inc., LGRED single-zone convertible mid-static ducted indoor units with LUU180HHV / LUU240HHV outdoor units) · checked 2026-08-25
- Defining Common Error Codes - Standard Wall-Mounted High-Efficiency Single Zone Systems (LG Electronics U.S.A. - Commercial Air Conditioning, LS091HSV and LS121HSV systems (LSN091HSV / LSN121HSV indoor units, LSU091HSV / LSU121HSV outdoor units)) · checked 2026-08-25
Code CH67: Outdoor BLDC fan motor lock error
Outdoor BLDC fan motor lock error. The outdoor fan is not turning when the board tells it to - usually something is physically jamming it (ice, leaves, a stick), or the motor or its connector has failed.
Manual wording: “Outdoor unit brushless direct current (BLDC) fan motor lock error”
Documented for: All LG residential mini-split outdoor units with BLDC fan motors
Likely causes, most common first
- Fan locked by physical force (foreign object stuck in the motor or blade)
- Poor connection of the motor connector
- Motor failure
- PCB failure
What you can safely check yourself
- Turn the outdoor unit off at the breaker first, then look through the grille for leaves, sticks, ice, or debris jamming the fan blade
- Clear snow and ice from around, under, and on top of the outdoor unit
- Once the obstruction is removed and the breaker is back on, try the system again
When to call a technician
If nothing is jamming the fan and CH67 returns, the fan motor or the outdoor control board has failed. Never reach into the outdoor fan with power on.
A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- MULTI F / MULTI F MAX Outdoor Unit Installation Manual (LG Electronics U.S.A., Inc., Multi F and Multi F MAX multi-zone heat pump outdoor units (LMU series) with standard wall-mount, Art Cool, cassette and ducted indoor units) · checked 2026-08-25
- Single Zone Four-Way Ceiling-Cassette Installation Manual (LG Electronics U.S.A., Inc., Single-zone four-way ceiling cassette indoor units with LUU090HV through LUU420HV outdoor units) · checked 2026-08-25
- Convertible Mid-Static Ducted LGRED Degree System Installation Manual (LG Electronics U.S.A., Inc., LGRED single-zone convertible mid-static ducted indoor units with LUU180HHV / LUU240HHV outdoor units) · checked 2026-08-25
- Defining Common Error Codes - Standard Wall-Mounted High-Efficiency Single Zone Systems (LG Electronics U.S.A. - Commercial Air Conditioning, LS091HSV and LS121HSV systems (LSN091HSV / LSN121HSV indoor units, LSU091HSV / LSU121HSV outdoor units)) · checked 2026-08-25
- Room Air Conditioner SVC Manual (General) - Trouble Shooting Guide with Error Code (LG Electronics, All LG single-zone room air conditioner / mini-split chassis (SW, SB, SC, S4, S5, SH, SA, SJ, SK)) · checked 2026-08-25