LG Mini-Split Code CH05
Soft lockoutShown as: Indoor unit LED1 (units place) blinks 5 times
Communication error between the indoor unit and the outdoor unit. The indoor unit's control board is not receiving a signal from the outdoor unit. This is the single most common LG mini-split code and it usually means the outdoor unit has no power or the interconnecting wiring is wrong or loose.
Manual wording: “Indoor unit PCB is not receiving signal from outdoor unit.”
Documented for: All LG residential mini-splits, single-zone and multi-zone
Likely causes, most common first
- No power on the indoor unit
- Indoor/outdoor unit power connection error, or the communication line was never installed
- Improper connection at the terminal block for the communication wire
- Improper wiring of the communication L-N wire between indoor and outdoor units
- Communication error caused by external electrical noise
- Indoor/outdoor communication circuit parts burned, or no power due to a burned indoor or outdoor PCB
What you can safely check yourself
- Check the breakers for BOTH the indoor and outdoor unit are on and not tripped
- Check the outdoor disconnect switch next to the condenser is switched on
- Turn the system off at the breaker for one minute, then back on
When to call a technician
If power is confirmed on at both units and CH05 stays, the interconnecting communication wiring or one of the control boards is at fault. Terminal-block and low-voltage work is a technician job.
A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Single Zone Four-Way Ceiling-Cassette Installation Manual (LG Electronics U.S.A., Inc., Single-zone four-way ceiling cassette indoor units with LUU090HV through LUU420HV outdoor units) · checked 2026-08-25
- MULTI F / MULTI F MAX Outdoor Unit Installation Manual (LG Electronics U.S.A., Inc., Multi F and Multi F MAX multi-zone heat pump outdoor units (LMU series) with standard wall-mount, Art Cool, cassette and ducted indoor units) · checked 2026-08-25
- Convertible Mid-Static Ducted LGRED Degree System Installation Manual (LG Electronics U.S.A., Inc., LGRED single-zone convertible mid-static ducted indoor units with LUU180HHV / LUU240HHV outdoor units) · checked 2026-08-25
- Defining Common Error Codes - Standard Wall-Mounted High-Efficiency Single Zone Systems (LG Electronics U.S.A. - Commercial Air Conditioning, LS091HSV and LS121HSV systems (LSN091HSV / LSN121HSV indoor units, LSU091HSV / LSU121HSV outdoor units)) · checked 2026-08-25
- Room Air Conditioner SVC Manual (General) - Trouble Shooting Guide with Error Code (LG Electronics, All LG single-zone room air conditioner / mini-split chassis (SW, SB, SC, S4, S5, SH, SA, SJ, SK)) · checked 2026-08-25