HVAC Code Lookup

LG Mini-Split: 3 Flashes

A LG mini-split LED pattern starting with 3 flashes matches 9 documented codes: CH03, CH31, CH32, CH34, CH35, CH36, CH37, CH38, CH39. Watch the full pattern (short vs. long flashes) to tell them apart — all 9 are explained below.

Code CH03: Wired remote controller

Soft lockoutShown as: Indoor unit LED1 (units place) blinks 3 times

Wired remote controller (thermostat) communication error. The indoor unit's control board is not receiving a signal from the wired wall controller. On systems that never had a wired controller, it usually means the controller connector on the board is dirty, wet or shorted.

Manual wording: “Indoor unit PCB is not receiving a signal from the wired remote controller (if installed).

Documented for: All LG residential mini-split indoor units with an optional wired remote controller

Likely causes, most common first

  1. Interference between the AC power line and the wired remote control line (wires twisted together or not separated)
  2. Poor contact or disconnection between the wired remote control DC line and the PCB harness
  3. PCB harness flooding or corrosion
  4. Wired remote control fault
  5. Indoor unit PCB fault

What you can safely check yourself

  • Turn the system off at the breaker for one minute, then back on
  • If a wired wall controller is installed, check it is not physically damaged or wet
  • Check the wall controller's display is lit at all

When to call a technician

Anything past a power cycle means opening the indoor unit or the controller and checking low-voltage wiring - call a technician.

A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Sources

Full page for LG code CH03

Code CH31: Current transformer

Soft lockoutShown as: Outdoor LED1 blinks 3 times, LED2 blinks 1 time

Current transformer (CT) reading is too low - the outdoor board is not sensing the current it expects for the compressor speed it commanded.

Manual wording: “Current to the current transformer (CT) thermistor is too low.

Documented for: LS091HSV / LS121HSV systems (LSN091HSV / LSN121HSV indoor, LSU091HSV / LSU121HSV outdoor)

Likely causes, most common first

  1. Current to the current transformer (CT) thermistor is too low

What you can safely check yourself

  • Turn the system off at the breaker for three minutes and back on

When to call a technician

The current transformer sits on the outdoor inverter board. Diagnosis is technician work.

A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Source

Full page for LG code CH31

Code CH32: Inverter compressor discharge pipe

Soft lockoutShown as: Outdoor LED01 (red) blinks 3 times, LED02 (green) blinks 2 times

Inverter compressor discharge pipe (D-pipe) temperature is too high. The gas leaving the compressor is overheating, which most often means the outdoor unit cannot reject heat or the system is low on refrigerant.

Manual wording: “Inverter compressor discharge pipe (D-Pipe) temperature is too high

Documented for: All LG residential mini-split outdoor units

Likely causes, most common first

  1. Overload operation - outdoor fan restricted, screened, or blocked
  2. Poor inverter compressor discharge sensor
  3. Refrigerant leakage (insufficient charge)
  4. EEV connector displaced or poor EEV (electronic expansion valve) assembly

What you can safely check yourself

  • Clear leaves, grass clippings, snow, or debris away from the outdoor coil and fan
  • Remove anything stacked against or on top of the outdoor unit
  • Check and clean the indoor air filters
  • Give the unit time to cool down, then turn it off at the breaker for three minutes and back on

When to call a technician

If airflow is clear and CH32 returns, the system is likely low on refrigerant or the expansion valve is misbehaving. Both require a licensed technician with gauges.

A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Sources

Full page for LG code CH32

Code CH34: High pressure sensor error

Soft lockoutShown as: Outdoor LED1 blinks 3 times, LED2 blinks 4 times (2-LED type; the service manual pairs CH34 with CH35 in one row)

High pressure sensor error (high) - the outdoor unit is reading discharge pressure above its limit. Typically the condenser cannot reject heat, or the charge is off.

Manual wording: “High pressure sensor error (high)

Documented for: LG single-zone room air conditioner / mini-split outdoor units fitted with pressure sensors

Likely causes, most common first

  1. Overload operation - outdoor fan restricted, screened, or blocked
  2. Refrigerant leakage (insufficient charge)
  3. Bad connection of the pressure sensor
  4. Bad compressor sensor
  5. Bad PCB

What you can safely check yourself

  • Clear leaves, grass clippings, snow, or debris away from the outdoor coil and fan
  • Remove anything stacked against or on top of the outdoor unit
  • Check and clean the indoor air filters

When to call a technician

Pressure faults require gauges and a licensed technician. Do not open, tighten or bypass anything on the refrigerant side.

A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Source

Full page for LG code CH34

Code CH35: Low pressure error - suction pressure has dropped below the recommended limit

Soft lockoutShown as: Outdoor LED01 (red) blinks 3 times, LED02 (green) blinks 5 times

Low pressure error - suction pressure has dropped below the recommended limit. Usually low refrigerant charge, a restriction, or badly blocked indoor airflow.

Manual wording: “Low Pressure Error; Pressure dropped below recommended limits

Documented for: All LG residential mini-split outdoor units fitted with pressure sensors

Likely causes, most common first

  1. Overload operation - outdoor fan restricted, screened, or blocked
  2. Refrigerant leakage (insufficient charge)
  3. Bad connection of the pressure sensor
  4. Bad compressor sensor
  5. Bad PCB

What you can safely check yourself

  • Check and clean the indoor air filters
  • Make sure the indoor supply and return grilles are open and unblocked
  • Clear leaves, grass clippings, snow, or debris away from the outdoor coil

When to call a technician

Low pressure almost always means the system has lost refrigerant. Refrigerant work is EPA-regulated - call a licensed technician.

A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Sources

Full page for LG code CH35

Code CH36: Refrigerant leakage detection

Hard lockoutShown as: Outdoor LED1 blinks 3 times, LED2 blinks 6 times (2-LED type; service manual lists this row as '36 (38)')

Refrigerant leakage detection. The outdoor unit's control logic has concluded the system is short on refrigerant.

Manual wording: “Refrigerant leakage detection

Documented for: LG single-zone room air conditioner / mini-split outdoor units with leak detection logic

Likely causes, most common first

  1. Pipe break damage
  2. Bad connection of the pipe (flare joints)
  3. Pipe damage due to corrosion
  4. Corrosion damage of the heat exchanger
  5. Compressor damage (crack)
  6. EEV body clogging
  7. Refrigerant shortage, including too little refrigerant added at install for the line length

What you can safely check yourself

  • Turn the system off so the compressor is not running short of refrigerant until a technician can look at it

When to call a technician

Refrigerant leak repair and recharging are EPA-regulated and require a licensed technician with recovery equipment. Do not add refrigerant yourself.

A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Source

Full page for LG code CH36

Code CH37: Compression ratio limit exceeded

Soft lockoutShown as: Outdoor LED1 blinks 3 times, LED2 blinks 7 times (2-LED type)

Compression ratio limit exceeded. The ratio between discharge and suction pressure is outside the compressor's safe envelope, so the unit stops. Points at a restriction, a closed service valve, or a charge problem.

Manual wording: “Failure compressing ratio

Documented for: LG single-zone room air conditioner / mini-split outdoor units

Likely causes, most common first

  1. Overload operation - outdoor fan restricted, screened, or blocked
  2. Service (SVC) valve locked or left closed
  3. Bad compressor sensor
  4. EEV connector displaced or poor EEV assembly
  5. EEV body clogging
  6. Refrigerant leakage (insufficient charge)
  7. Refrigerant overcharge

What you can safely check yourself

  • Clear leaves, grass clippings, snow, or debris away from the outdoor coil and fan
  • Check and clean the indoor air filters

When to call a technician

A closed service valve, a clogged expansion valve, or an incorrect charge all need a licensed technician with gauges. Never operate the service valves yourself.

A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Source

Full page for LG code CH37

Code CH38: Refrigerant leakage detection - the system is low on refrigerant

Hard lockoutShown as: Outdoor LED1 blinks 3 times, LED2 blinks 6 times (2-LED type; service manual lists this row as '36 (38)')

Refrigerant leakage detection - the system is low on refrigerant. LG's consumer support page states plainly that CH38 means the air conditioner is low on refrigerant (gas).

Manual wording: “Refrigerant leakage detection

Documented for: LG residential mini-split outdoor units with refrigerant leak detection (including LSU363HLV-class dual inverter units)

Likely causes, most common first

  1. Pipe break damage
  2. Bad connection of the pipe (flare joints)
  3. Pipe damage due to corrosion
  4. Corrosion damage of the heat exchanger
  5. Compressor damage (crack)
  6. EEV body clogging
  7. Refrigerant shortage, including too little refrigerant added at install for the line length

What you can safely check yourself

  • Turn the system off so the compressor is not running short of refrigerant until a technician can look at it

When to call a technician

A leak has to be found, repaired, and the system evacuated and recharged by weight. That is EPA-regulated work for a licensed technician - topping it off without finding the leak just repeats the failure.

A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Sources

Full page for LG code CH38

Code CH39: Communication error between the PFC MICOM and the inverter MICOM - the two microcontrollers on the outdoor unit's power board have lost contact with each other

Soft lockoutShown as: Outdoor LED01 (red) blinks 3 times, LED02 (green) blinks 9 times

Communication error between the PFC MICOM and the inverter MICOM - the two microcontrollers on the outdoor unit's power board have lost contact with each other.

Manual wording: “Communication Error between PFC MICOM and Inverter MICOM

Documented for: LG Multi F / Multi F MAX outdoor units

What you can safely check yourself

  • Turn the system off at the breaker for three minutes and back on

When to call a technician

This is an internal fault between processors on the outdoor inverter board. A technician has to diagnose and usually replace the board.

A LG mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Source

Full page for LG code CH39

Other LG codes