Fujitsu Mini-Split: 9 Flashes

A Fujitsu mini-split LED pattern starting with 9 flashes matches 5 documented codes: 94, 95, 97, 98, 99. Watch the full pattern (short vs. long flashes) to tell them apart — all 5 are explained below.

Code 94: Over current error

Soft lockoutShown as: OPERATION lamp blinks 9 times, TIMER lamp blinks 4 times, ECONOMY lamp blinking continuously

Over current error (trip detection). The compressor tripped on overcurrent immediately after starting, ten times consecutively, so the unit shut down.

Manual wording: “Over Current Error - Protection stop by overcurrent generation after inverter compressor start processing completed generated consecutively 10 times.

Documented for: RL2, RLS2, RLS3, RLB/RLXB, RLF, RLF1, RGLX, RLE, LUAS1, LMAS, LZBS, LZAS, LPAS series

Likely causes, most common first

  1. Clogged outdoor heat exchanger restricting airflow
  2. Defective condenser fan motor
  3. Discharged air being pulled back into the outdoor unit (short cycling of air)
  4. Compressor or inverter fault

What you can safely check yourself

  • Check the outdoor coil for heavy dirt, cottonwood, grass clippings, or leaves and clear away anything blocking it
  • Make sure the outdoor unit has clearance on all sides and its discharge air is not blowing into a wall or fence and back into the coil
  • Turn the power off at the disconnect for about 5 minutes, then restore power

When to call a technician

If airflow is clear and the code returns, the condenser fan motor or the compressor circuit has to be tested by a licensed technician.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Sources

Full page for Fujitsu code 94

Code 95: Compressor motor control error

Hard lockoutShown as: OPERATION lamp blinks 9 times, TIMER lamp blinks 5 times, ECONOMY lamp blinking continuously

Compressor motor control error (rotor position detection error). The control cannot keep track of the compressor rotor position, so the compressor stops; if it repeats within 40 seconds of restart it stops again and can go to a permanent stop.

Manual wording: “Compressor Motor Control Error - If the detected rotor location is out of phase with actual rotor location more than 90 degrees, the compressor stops.

Documented for: RL2, RLS2, RLS3, RLB/RLXB, RLF, RLF1, RGLX, RLE, LUAS1, LMAS, LZBS, LZAS, LPAS series

Likely causes, most common first

  1. Connector removed or loose on the compressor leads
  2. Erroneous connection at the compressor terminals
  3. Open compressor lead cable
  4. Failed compressor or inverter board

What you can safely check yourself

  • Turn the power off at the outdoor disconnect and breaker for about 5 minutes, then restore power

When to call a technician

This is a compressor-drive fault. Compressor terminal and winding checks are high-voltage work for a licensed technician only.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Sources

Full page for Fujitsu code 95

Code 97: Outdoor unit fan motor error

Soft lockoutShown as: OPERATION lamp blinks 9 times, TIMER lamp blinks 7 times, ECONOMY lamp blinking continuously

Outdoor unit fan motor error. The outdoor fan turned slower than 100 RPM within 20 seconds of starting; after three repeats inside 60 seconds the compressor and fan both stop.

Manual wording: “Outdoor Unit Fan Motor Error - When outdoor fan motor rotation speed is less than 100 RPMs in 20 seconds after fan motor starts, fan motor stops.

Documented for: RL2, RLS2, RLS3, RLB/RLXB, RLF, RLF1, RGLX, RLE, LUAS1, LMAS, LZBS, LZAS, LPAS series

Likely causes, most common first

  1. Outdoor fan blade obstructed, iced, or the motor is locked
  2. Excessive ambient temperature around the fan motor from nearby heat-producing equipment
  3. Outdoor fan motor windings out of specification, or missing DC supply to the motor
  4. Failed outdoor main PCB

What you can safely check yourself

  • With the power off at the disconnect, look for leaves, ice, or debris jamming the outdoor fan blade
  • Clear snow and ice buildup from around and on top of the outdoor unit
  • Turn the power off at the disconnect for about 5 minutes, then restore power

When to call a technician

Fujitsu's next steps are ohming the fan motor windings and checking DC voltage to the motor. That means a licensed technician.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Sources

Full page for Fujitsu code 97

Code 98: Outdoor unit fan motor 2 error, on twin-fan condensers

Hard lockoutShown as: OPERATION lamp blinks 9 times, TIMER lamp blinks 8 times, ECONOMY lamp blinking continuously

Outdoor unit fan motor 2 error, on twin-fan condensers. The second outdoor fan turned slower than 100 RPM within 20 seconds of starting; repeated five times in a row, the compressor and fan stop permanently.

Manual wording: “Outdoor Unit Fan Motor 2 Error - When the outdoor fan rotation speed is less than 100 RPMs in 20 seconds after the fan motor starts, the fan will stop... If above repeats 5 times in a row, compressor and fan stop permanently.

Documented for: Twin-fan outdoor units: larger RGLX, RLXB and RLXFZ condensers

Likely causes, most common first

  1. Second outdoor fan blade obstructed, iced, or the motor is locked
  2. Excessive ambient temperature around the fan motor
  3. Fan motor windings out of specification, or missing DC voltage to the motor
  4. Failed outdoor main PCB

What you can safely check yourself

  • With the power off at the disconnect, look for debris or ice jamming either outdoor fan blade
  • Turn the power off at the disconnect for about 5 minutes, then restore power

When to call a technician

After the permanent stop this needs a technician to test the motor and reset the system.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Source

Full page for Fujitsu code 98

Code 99: 4-way

Soft lockoutShown as: OPERATION lamp blinks 9 times, TIMER lamp blinks 9 times, ECONOMY lamp blinking continuously

4-way (reversing) valve error. The control compared indoor coil temperature to room temperature and twice found the system running backwards for the selected mode, so the compressor stopped.

Manual wording: “4-Way Valve Error - When the indoor heat exchanger temperature is compared with the room temperature, and either following condition is detected continuously two times, the compressor stops.

Documented for: RL2, RLS2, RLS3, RLB/RLXB, RLF, RLF1, RGLX, RLE, LUAS1, LMAS, LZBS, LZAS, LPAS series

Likely causes, most common first

  1. 4-way valve stuck or not shifting
  2. Failed 4-way valve solenoid coil, or no voltage to the coil
  3. Loose molex plug at the valve coil
  4. Thermistor reading wrong (indoor coil or room sensor)

What you can safely check yourself

  • Note which mode the system was in when it failed - Fujitsu uses that to separate a valve fault from a control fault
  • Turn the power off at the disconnect for about 5 minutes and back on, then run the system and see whether it heats or cools correctly

When to call a technician

Testing the reversing valve, its solenoid coil, and the coil voltage is refrigeration and line-voltage work for a licensed technician.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Sources

Full page for Fujitsu code 99