Fujitsu Mini-Split Code 24

Soft lockoutShown as: OPERATION lamp blinks 2 times, TIMER lamp blinks 4 times, ECONOMY lamp blinking continuously

Number of indoor units error or number of branch boxes error. The total number of connected indoor units is outside the allowed range of 2 to 8, or the two branch boxes report a different number of units.

Manual wording: “Number of Indoor Units Error / Number of Branch Boxes Error - When the total connection number of indoor units is outside of range between 2 and 8.

Documented for: RLF / RLF1 multi-zone indoor units on branch-box (HFI Flex) systems

Likely causes, most common first

  1. Too many or too few indoor units connected for the outdoor unit
  2. A branch box not powered up
  3. Mismatch between branch box 1 and branch box 2 unit counts

What you can safely check yourself

  • Confirm the branch boxes still have power at their breakers or disconnects
  • Turn the whole system off at the breaker for about 5 minutes and back on

When to call a technician

Branch box configuration and unit counts are set at install. A technician has to verify the branch box power and the connected unit count.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.