HVAC Code Lookup

Bryant Furnace Code 32.2

WarningShown as: Major code 32 on the LED (3 short, 2 long); 32.2 on the display

Open main pressure switch. If the low-heat pressure switch stays open longer than 5 minutes or reopens, the inducer shuts off for 15 minutes before retrying. On a two-stage furnace this can force the next cycle to high heat only.

Manual wording: “32.2 OPEN MAIN PRESSURE SWITCH - If LPS is open longer than 5 minutes or has reopened, inducer shuts off for 15 minutes before retry.

Documented for: 926TC

Likely causes, most common first

  1. Restricted or improperly sized vent
  2. Plugged condensate drain
  3. Obstructed pressure tubing
  4. Defective inducer motor or pressure switch
  5. Excessive wind

What you can safely check yourself

  • Check outdoor vent terminations for snow, ice, or debris
  • Check the condensate drain and trap for a clog
  • Replace a dirty air filter

When to call a technician

Have a technician confirm vent sizing and pressure switch operation. Do not bypass the switch.

A Bryant furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.