HVAC Code Lookup

Mitsubishi Electric Mini-Split Code U7

Soft lockout

Too low superheat due to low discharge temperature. Discharge superheat stayed at 5F or below for 3 minutes even with the linear expansion valve at its minimum opening, meaning liquid refrigerant is likely reaching the compressor.

Manual wording: “Too low superheat due to low discharge temperature - Abnormal if discharge superheat is continuously detected less than or equal to 5F [-15C] for 3 minutes

Documented for: A-Control outdoor units (PUZ, MUZ, MXZ)

Likely causes, most common first

  1. Disconnection or loose connection of the discharge temperature thermistor (TH4)
  2. Defective high pressure or temperature sensing
  3. Disconnection or loose connection of the linear expansion valve or its connector
  4. Defective linear expansion valve
  5. Overcharge of refrigerant

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once

When to call a technician

Expansion valve and refrigerant charge problems require gauges and EPA certification. Call a technician.

A Mitsubishi Electric mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Source

Other Mitsubishi Electric codes