HVAC Code Lookup

Mitsubishi Electric Mini-Split Code P2

Soft lockout

Pipe temperature thermistor / liquid (TH2) error. The indoor liquid-line sensor reads short circuit (194F or more) or open circuit (-40F or less).

Manual wording: “Pipe temperature thermistor/Liquid (TH2) ... Short: 90C [194F] or more, Open: -40C [-40F] or less

Documented for: A-Control indoor units (PKA-A, PLA-A, PEAD-A and M-Series with a wired controller)

Likely causes, most common first

  1. Defective thermistor characteristics
  2. Contact failure of connector CN44 on the indoor controller board (insert failure)
  3. Breaking of wire or contact failure of thermistor wiring
  4. Defective refrigerant circuit driving the thermistor to 194F or more or -40F or less
  5. Defective indoor controller board

What you can safely check yourself

  • Turn the system off at the breaker, wait one minute, and turn it back on once to see if it resets

When to call a technician

If the pipe temperature really is that far out of range the refrigerant circuit is at fault, which is a technician job either way.

A Mitsubishi Electric mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.