Mitsubishi Electric Mini-Split Code P1
Soft lockout
Room temperature thermistor (TH1) error. The intake air temperature sensor reads short circuit (194F or more) or open circuit (-40F or less), so the unit cannot measure room temperature.
Manual wording: “Room temperature thermistor (TH1) ... Short: 90C [194F] or more, Open: -40C [-40F] or less”
Documented for: A-Control indoor units (PKA-A, PLA-A, PEAD-A and M-Series with a wired controller)
Likely causes, most common first
- Defective thermistor characteristics
- Contact failure of connector CN20 on the indoor controller board (insert failure)
- Breaking of wire or contact failure of thermistor wiring
- Defective indoor controller board
What you can safely check yourself
- Turn the system off at the breaker, wait one minute, and turn it back on once to see if it resets
When to call a technician
Checking the thermistor resistance and its connector means opening the indoor unit and working at the control board. Call a technician.
A Mitsubishi Electric mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Indoor Unit Service Manual No. OCH761 Revised Edition-A - PKA-A LA Series (May 2021) (Mitsubishi Electric, PKA-A12LA, PKA-A18LA, PKA-A12LA.TH, PKA-A18LA.TH wall-mounted indoor units) · checked 2026-08-25