Mitsubishi Electric Mini-Split Code E6
Soft lockout
Indoor/outdoor unit communication error (signal receiving error). The indoor controller board received no signal from the outdoor unit for 6 minutes after power-on, or for 3 minutes during operation. The most common cause is a problem with the wire running between the indoor and outdoor units.
Manual wording: “Indoor/outdoor unit communication error (Signal receiving error) - Abnormal if indoor controller board cannot receive any signal normally for 6 minutes after turning the power on.”
Documented for: A-Control indoor and outdoor units (M-Series and P-Series)
Likely causes, most common first
- Contact failure, short circuit or miswiring (reverse wiring) of the indoor/outdoor unit connecting wire
- Defective transmitting/receiving circuit of the indoor controller board
- Defective transmitting/receiving circuit of the outdoor controller board
- Noise has entered the indoor/outdoor unit connecting wire
What you can safely check yourself
- Check that the breaker feeding the outdoor unit is on and has not tripped
- Check that the outdoor unit is clear of snow, ice and debris and that nothing has damaged the wire cover
- Turn the system off at the breaker, wait one minute, and turn it back on once
When to call a technician
The S1-S2-S3 connecting wire carries line voltage. Checking, tightening or correcting it, and any board replacement, is a technician job.
A Mitsubishi Electric mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Indoor Unit Service Manual No. OCH761 Revised Edition-A - PKA-A LA Series (May 2021) (Mitsubishi Electric, PKA-A12LA, PKA-A18LA, PKA-A12LA.TH, PKA-A18LA.TH wall-mounted indoor units) · checked 2026-08-25
- Service Manual No. OCH750 Revised Edition-E - PUZ-HA Outdoor Units (May 2024) (Mitsubishi Electric, PUZ-HA24NHA1, PUZ-HA30NKA, PUZ-HA36NKA, PUZ-HA42NKA1 heat-pump outdoor units) · checked 2026-08-25