Mitsubishi Electric Mini-Split Code E3
Soft lockout
Remote controller transmission error. The remote controller could not find a free slot on the transmission path for 6 seconds and could not transmit, or its sent and received data disagreed 30 times in a row.
Manual wording: “Remote controller transmission error(E3)/signal receiving error(E5) - Abnormal if remote controller could not find blank of transmission path for 6 seconds and could not transmit.”
Documented for: A-Control systems with a wired remote controller
Likely causes, most common first
- Two remote controllers are both set as 'main'
- One remote controller is connected to 2 or more indoor units
- Repetition of refrigerant address
- Defective transmitting/receiving circuit of the remote controller or the indoor controller board
- Noise has entered the remote controller transmission wire
What you can safely check yourself
- Turn the system off at the breaker, wait one minute, and turn it back on once
When to call a technician
Setting main/sub, checking addresses and diagnosing the controller are technician tasks.
A Mitsubishi Electric mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.