Fujitsu Mini-Split: 10 Flashes

A Fujitsu mini-split LED pattern starting with 10 flashes matches 3 documented codes: A1, A3, A5. Watch the full pattern (short vs. long flashes) to tell them apart — all 3 are explained below.

Code A1: Discharge temperature error

Soft lockoutShown as: OPERATION lamp blinks 10 times, TIMER lamp blinks 1 time, ECONOMY lamp blinking continuously

Discharge temperature error. The compressor discharge line reached 230 F (110 C) during operation twice within 24 hours, so the system stopped to protect the compressor.

Manual wording: “Discharge Temperature Error - Protection stop by discharge temperature 230F (110C) during compressor operation generated 2 times within 24 hours.

Documented for: RL2, RLS2, RLS3, RLB/RLXB, RLF, RLF1, RGLX, RLE, LUAS1, LMAS, LZBS, LZAS, LPAS series

Likely causes, most common first

  1. Closed or partly closed 3-way service valve
  2. Restricted electronic expansion valve or clogged strainer
  3. Outdoor fan or heat exchanger not rejecting heat (dirty coil, blocked airflow)
  4. Low refrigerant charge or a refrigerant leak
  5. Failed discharge thermistor

What you can safely check yourself

  • Clear anything blocking airflow at the outdoor unit - leaves, snow, stored items, overgrown shrubs
  • Check the outdoor coil for heavy dirt or cottonwood buildup
  • Turn the power off at the disconnect for about 5 minutes, then restore power

When to call a technician

Fujitsu's checklist is service valves, expansion valve, strainer, and a leak check with gauges. All of that is licensed refrigeration work - do not open service valves yourself.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Sources

Full page for Fujitsu code A1

Code A3: Compressor temperature error

Soft lockoutShown as: OPERATION lamp blinks 10 times, TIMER lamp blinks 3 times, ECONOMY lamp blinking continuously

Compressor temperature error. The compressor body reached 226 F (107.8 C) during operation twice within 24 hours and the system stopped to protect it.

Manual wording: “Compressor Temperature Thermistor Error - Protection stop by compressor temperature 226F (107.8C) during compressor operation generated 2 times within 24 hours.

Documented for: RL2, RLS2, RLS3, RLB/RLXB, RLF, RLF1, RGLX, RLE, LUAS1, LMAS, LZBS, LZAS, LPAS series

Likely causes, most common first

  1. Closed or partly closed 3-way service valve
  2. Restricted electronic expansion valve or clogged strainer
  3. Outdoor fan or heat exchanger not rejecting heat
  4. Low refrigerant charge or a leak
  5. Loose connection at the compressor thermistor

What you can safely check yourself

  • Clear leaves, snow, and debris from around the outdoor unit and off the coil
  • Turn the power off at the disconnect for about 5 minutes, then restore power

When to call a technician

Service valve position, expansion valve, strainer and charge level all require gauges and a refrigeration license. Call a technician.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.

Sources

Full page for Fujitsu code A3

Code A5: Low pressure error

Soft lockoutShown as: OPERATION lamp blinks 10 times, TIMER lamp blinks 5 times, ECONOMY lamp blinking continuously

Low pressure error. Suction pressure stayed at or below 7.35 PSI for 5 minutes, repeating 5 times within 2 hours, so the system stopped.

Manual wording: “Low Pressure Error - Protection stop by suction pressure 7.35 PSI continued for 5 minutes, repeats 5 times within 2 hours.

Documented for: Single-zone (1-to-1) matched systems; RGLX, RLS3/RLB/RLXB, RLF/RLF1

Likely causes, most common first

  1. Closed or partly closed 3-way (gas side) service valve
  2. Clogged strainer
  3. Failed electronic expansion valve coil
  4. Low refrigerant charge or a refrigerant leak
  5. Failed suction pressure sensor

What you can safely check yourself

  • Note the outdoor temperature when the code appeared - Fujitsu says this code only shows up when outdoor ambient drops below 32 F
  • Turn the power off at the disconnect for about 5 minutes, then restore power

When to call a technician

Fujitsu classes A5 as a fix-on-fail code that must be serviced on site by a licensed technician, with running pressures checked on gauges and a leak check performed. It also requires function setting F3-40 to fully reset.

A Fujitsu mini-split throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.