Coleman Furnace: 3 Flashes
A Coleman furnace LED pattern starting with 3 flashes matches 5 documented codes: 3 red flashes, 3 green flashes, 3 green flashes (CP9C Echelon modulating), 3 amber flashes (CP9C Echelon modulating), 3 red flashes (CP9C Echelon modulating). Watch the full pattern (short vs. long flashes) to tell them apart — all 5 are explained below.
Code 3 red flashes: The pressure switch contacts are open when they should be closed
The pressure switch contacts are open when they should be closed. The inducer is not producing enough draft to close the switch, so the control will not light the burners.
Manual wording: “3 RED FLASHES: This indicates the pressure switch contacts are open when they should be closed. Check for faulty inducer, blocked vent pipe, broken pressure switch hose, disconnected pressure switch or inducer wires or faulty pressure switch.”
Documented for: TG8S, TGLS, TG9S, TM8X, TMLX, TM9X, TM8T, TM9T, TM8V, TM9V
Likely causes, most common first
- Faulty inducer (draft) motor
- Blocked vent pipe
- Broken pressure switch hose
- Disconnected pressure switch or inducer wires
- Faulty pressure switch
What you can safely check yourself
- Go outside and check the vent and combustion air pipe terminations for snow, ice, leaves, insect nests or other blockage
- Check the condensate drain and trap for a clog (on 90%+ furnaces a plugged drain can back up and open the pressure switch)
- Replace a heavily clogged air filter
When to call a technician
If the outside pipes are clear and the code stays, a technician needs to test the inducer, hoses and switch. Do not jumper the pressure switch - it is what proves the furnace can vent safely.
A Coleman furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Installation Manual - Residential Gas Furnace, Models TG9S*MP, GG9S*MP (95.5% AFUE Single Stage Multi-position), 364861-UIM-G-1211 (Johnson Controls Unitary Products (Coleman), TG9S*MP, GG9S*MP 95.5% AFUE single-stage multi-position gas furnaces) · checked 2026-08-25
- Installation Manual - Residential Gas Furnace, Models TG8S*MP, TGLS*MP, GG8S*MP, GGLS*MP (Single Stage Multi-position / Low NOx), 356485-UIM-G-1211 (Johnson Controls Unitary Products (Coleman), TG8S*MP, TGLS*MP, GG8S*MP, GGLS*MP 80% AFUE single-stage gas furnaces) · checked 2026-08-25
- Installation Manual - Residential Gas Furnace, Models TM8X*MP, TMLX*MP (Single Stage Multi-position / Low NOx with High-Efficiency Motors), 437642-UIM-F-1211 (Johnson Controls Unitary Products (Coleman), TM8X*MP, TMLX*MP 80% AFUE single-stage gas furnaces with high-efficiency motors) · checked 2026-08-25
- Installation Manual - Residential Gas Furnace, Models TM9V*MP (Two Stage Variable Speed ECM), 701379-UIM-B-1211 (Johnson Controls Unitary Products (Coleman), TM9V*MP two-stage variable-speed ECM gas furnaces) · checked 2026-08-25
Code 3 green flashes: Confirmation that the stored error code memory has been cleared
Confirmation that the stored error code memory has been cleared. Not a fault.
Manual wording: “The LED will flash three green flashes when the memory has been cleared, then will resume the normal slow green flash after a five-second pause.”
Documented for: All Coleman UPG boards with a LAST ERROR button
Likely causes, most common first
- The LAST ERROR button was held for more than five seconds, clearing the fault history
When to call a technician
Not a fault. Clearing the fault history erases the evidence a technician uses to diagnose an intermittent problem, so leave the button alone before a service visit.
A Coleman furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Sources
- Installation Manual - Residential Gas Furnace, Models TG9S*MP, GG9S*MP (95.5% AFUE Single Stage Multi-position), 364861-UIM-G-1211 (Johnson Controls Unitary Products (Coleman), TG9S*MP, GG9S*MP 95.5% AFUE single-stage multi-position gas furnaces) · checked 2026-08-25
- Installation Manual - Residential Gas Furnace, Models TM9V*MP (Two Stage Variable Speed ECM), 701379-UIM-B-1211 (Johnson Controls Unitary Products (Coleman), TM9V*MP two-stage variable-speed ECM gas furnaces) · checked 2026-08-25
Code 3 green flashes (CP9C Echelon modulating): Indicator for 'Error codes cleared from memory'
Indicator for 'Error codes cleared from memory'. Not a fault.
Manual wording: “Three Green Flashes - Indicator for "Error codes cleared from memory".”
Documented for: CP9C Echelon modulating furnaces
Likely causes, most common first
- The stored fault history was cleared with the LAST ERROR button
When to call a technician
Not a fault, but clearing the history erases what a technician needs to chase an intermittent problem - leave it alone before a service visit.
A Coleman furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Installation Manual - Residential Gas Furnace with ECM Motor, Models TP9C*C, YP9C*C, CP9C*C, LP9C*C (Up to 98% Modulating Multi-position), 681292-UIM-B-1211 (Johnson Controls Unitary Products (Coleman), CP9C*C Coleman Echelon modulating gas furnace (manual also covers the identical TP9C, YP9C and LP9C chassis)) · checked 2026-08-25
Full page for Coleman code 3 green flashes (CP9C Echelon modulating)
Code 3 amber flashes (CP9C Echelon modulating): Normal operation - the burner is still on at the end of the heating cycle after the wall thermostat has been satisfied
Normal operation - the burner is still on at the end of the heating cycle after the wall thermostat has been satisfied. Not a fault.
Manual wording: “Three Amber flashes - Normal operation, burner is on at end of heating cycle after wall thermostat has been satisfied.”
Documented for: CP9C Echelon modulating furnaces
Likely causes, most common first
- Normal end-of-cycle burner operation on the modulating control
When to call a technician
No service needed.
A Coleman furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Installation Manual - Residential Gas Furnace with ECM Motor, Models TP9C*C, YP9C*C, CP9C*C, LP9C*C (Up to 98% Modulating Multi-position), 681292-UIM-B-1211 (Johnson Controls Unitary Products (Coleman), CP9C*C Coleman Echelon modulating gas furnace (manual also covers the identical TP9C, YP9C and LP9C chassis)) · checked 2026-08-25
Full page for Coleman code 3 amber flashes (CP9C Echelon modulating)
Code 3 red flashes (CP9C Echelon modulating): The pressure switch is open while inducer pressure is above the switch setpoint - the switch is open when it should be closed, so the burners cannot light
The pressure switch is open while inducer pressure is above the switch setpoint - the switch is open when it should be closed, so the burners cannot light.
Manual wording: “Three Red Flashes - Pressure switch open with inducer pressure above pressure switch setpoint (switch is open when it should be closed). Check pressure switch.”
Documented for: CP9C Echelon modulating furnaces
Likely causes, most common first
- Faulty pressure switch
What you can safely check yourself
- Check the outside vent and intake pipe terminations for snow, ice, leaves or nests
- Check the condensate drain and trap for a clog
When to call a technician
If the venting and drain are clear, the pressure switch needs a technician with a manometer.
A Coleman furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.
Source
- Installation Manual - Residential Gas Furnace with ECM Motor, Models TP9C*C, YP9C*C, CP9C*C, LP9C*C (Up to 98% Modulating Multi-position), 681292-UIM-B-1211 (Johnson Controls Unitary Products (Coleman), CP9C*C Coleman Echelon modulating gas furnace (manual also covers the identical TP9C, YP9C and LP9C chassis)) · checked 2026-08-25
Full page for Coleman code 3 red flashes (CP9C Echelon modulating)