Ruud Furnace Code 11

Soft lockout

Failed ignition. The furnace opened the gas valve but never proved a flame. It retries with a 20-second post-purge between attempts; after the fourth consecutive failure it goes to a one-hour lockout and alternates 11 with 10.

Manual wording: “FAILED IGNITION ... This fault is displayed at the furnace control after the first failed ignition attempt. ... After four failed ignition attempts, the IFC enters one-hour lockout and the dual faults "11" and "10" are alternately displayed.

Documented for: (-)97V, (-)96V, (-)801S/(-)801P

Likely causes, most common first

  1. The flame sense rod is unable to sense flame - it may need cleaning or may not be properly connected
  2. The gas valve may be turned off
  3. The igniter is not working properly, is not properly connected, or the spark location is not correct
  4. The furnace control may not be working properly and may need to be replaced
  5. The flame may not be properly spreading from the first burner to the last

What you can safely check yourself

  • Check that the furnace doors are fully seated and latched.
  • Check and replace a dirty air filter.
  • Try one power cycle at the furnace switch or breaker to clear the lockout.
  • Check the outdoor intake and exhaust terminations for snow, ice or debris.

When to call a technician

If the code returns, the flame sensor, igniter, gas valve or gas supply needs a technician. Do not open the burner compartment or touch the gas valve, flame sensor or igniter yourself.

A Ruud furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.