Rheem Furnace Code 58

Soft lockout

Water circuit open. The control cannot see continuity between pins 1 and 2 of connector P4, which is how it verifies both collector-box water sensors are present and wired. Gas heat is blocked; cooling still runs.

Manual wording: “WATER CIRCUIT OPEN ... The IFC cannot detect electrical continuity between pins 1 and 2 of connector P4 of the furnace control.

Documented for: (-)97V, (-)96V condensing furnaces

Likely causes, most common first

  1. Wiring has been damaged between the control or sensor
  2. Connection of P4 at the IFC or at the water sensors is not properly made
  3. Water sensor has been removed

When to call a technician

The water sensors and their wiring are inside the furnace - a technician needs to repair the connection or replace a missing sensor.

A Rheem furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.