HVAC Code Lookup

Carrier Furnace Code 24

Hard lockoutShown as: 2 short flashes, 4 long flashes

The 3-amp secondary voltage fuse on the control board is blown, which means there is a short somewhere in the 24 V low-voltage wiring.

Manual wording: “24 SECONDARY VOLTAGE FUSE IS OPEN - Check for: - Short circuit in secondary voltage (24V) wiring including thermostat leads.

Documented for: 58SC0A, 58MCB, 58MVP, 58UVB

Likely causes, most common first

  1. Short circuit in the 24 VAC secondary wiring, including the thermostat leads

When to call a technician

Replacing the fuse without finding the short just blows the new fuse. A technician needs to isolate the shorted thermostat or accessory wire.

A Carrier furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.