HVAC Code Lookup

Carrier Furnace Code 21

Hard lockoutShown as: 2 short flashes, 1 long flash

Gas heating lockout. The control detected 24 VAC on the gas valve when it should not be there. This lockout does NOT auto-reset.

Manual wording: “21 GAS HEATING LOCKOUT - Control will NOT auto reset. Check for: - Mis-wired gas valve. - Defective control (valve relay).

Documented for: 58SC0A, 58MCB, 58MVP, 58UVB

Likely causes, most common first

  1. Stuck-closed gas valve relay on the control board
  2. Mis-wired or shorted gas valve wire

When to call a technician

Code 21 means the control can no longer guarantee it can shut the gas valve off. Shut the furnace off at the service switch and call a technician - this one does not clear on its own.

A Carrier furnace throwing this code repeatedly has a reason — clearing the code without fixing the cause just hides it.